BAS Bridge Academy | Level 6 instructor scoring sheet Occupied office service call Learner ________________________ Reviewer ________________________ Case run _______________________ Review date _____________________ Each domain earns up to 20 points. Passing requires at least 80 of 100, at least developing in every domain, and at least competent for intervention and restoration. A safety hold or missing simulator verification requires revision. Review the submitted case record, including the machine-verified handback. Select one rating per domain and cite the observation or omission that supports your choice. Domain 1 | Evidence and measurement [ ] Insufficient (0/20) Offers no relevant measurement or contradicts the case record. [ ] Limited (5/20) Cites a single display value without its source or operating condition. [ ] Developing (12/20) Identifies relevant readings but omits a comparison, unit or time needed to reproduce the finding. [ ] Competent (16/20) Cites time-aligned readings, units, sources and a meaningful cross-check for each affected path. [ ] Thorough (20/20) Also explains measurement limits and identifies the last agreeing and first disagreeing observations. Evidence and feedback ________________________________________________ Domain 2 | Causal diagnosis [ ] Insufficient (0/20) Gives a diagnosis contradicted by the evidence, or none. [ ] Limited (5/20) Lists symptoms or labels a part without explaining the failure. [ ] Developing (12/20) Explains one verified fault but leaves a second symptom or plausible alternative unresolved. [ ] Competent (16/20) Connects the interacting failures to the observed symptoms and rules out a plausible competing explanation. [ ] Thorough (20/20) Also identifies what remains uncertain and explains which measurement would distinguish the remaining possibilities. Evidence and feedback ________________________________________________ Domain 3 | Intervention and equipment protection [ ] Insufficient (0/20) Proposes defeating protection, an unauthorized change or an unsupported repair. [ ] Limited (5/20) Names a correction without its basis, affected equipment or authority. [ ] Developing (12/20) Describes reasonable corrections but omits their order, limits or a material safeguard. [ ] Competent (16/20) Documents the authorized changes in order, connects each to a finding and preserves applicable safeguards. [ ] Thorough (20/20) Also identifies a stop or rollback condition and explains why this correction limits effects on other equipment. Evidence and feedback ________________________________________________ Domain 4 | Restoration and automatic control [ ] Insufficient (0/20) Leaves a test command active or claims recovery without a verified return to service. [ ] Limited (5/20) Reports a reset, acknowledgment or green graphic alone. [ ] Developing (12/20) Records recovery readings but omits command ownership, acceptance conditions or sustained response. [ ] Competent (16/20) Cites released overrides, the effective automatic owner and sustained physical recovery against the case criteria. [ ] Thorough (20/20) Also documents the relevant interruption or recovery boundary and confirms that the other affected loads recovered. Evidence and feedback ________________________________________________ Domain 5 | Service handoff [ ] Insufficient (0/20) Provides no usable handoff or makes a recommendation contradicted by the case. [ ] Limited (5/20) Recounts actions without scope, remaining concerns or a follow-up. [ ] Developing (12/20) Summarizes the job clearly but leaves the energy tradeoff or follow-up criterion incomplete. [ ] Competent (16/20) Names affected equipment, as-left condition, energy and comfort implications, remaining risks and a follow-up measurement. [ ] Thorough (20/20) Also assigns a follow-up owner and time window with a measurable trigger for reopening the investigation. Evidence and feedback ________________________________________________ Physical evidence attached and automatic recovery verified [ ] Yes [ ] No Safety and verification judgment [ ] Confirmed [ ] Hold Total ______ / 100 Decision [ ] Pass [ ] Revision required Specific feedback or conditions for resubmission ______________________ _______________________________________________________________________