BAS Bridge
System explorer

Air handling system

AHU-02 Supply air handler

Fan proven
Simulation settings

Air path and operating points

Occupied cooling

FAN → COILSSelectedDAT 55.3°FRead-only

Select Enlarge detail to inspect readings at full size.

AHU-02 equipment and live training pointsAir-handling unit cutaway with fan before the coil. Fan command ON; fan proof ON. Read command, proof, and response. Point values are supplied by the training simulation. A dash denotes unavailable data. Motion indicates proof, not a calibrated speed or flow measurement. Select a point tag to inspect its details.OUTDOOR + RETURN AIR → CONDITIONING → SUPPLYBLOW-THROUGHSELECT ANY POINT TO INSPECTMIXING BOXFILTER BANKSUPPLY FANHEATING COILCOOLING COILSUPPLY AIROutdoor-air temperatureOAT84.0°FOutdoor airReturn-air temperatureRAT71.6°FReturn airOutdoor-air damper commandOAD-CMD25% CMDDamper commandMixed-air temperatureMAT73.2°FMixed airOutdoor-air damper feedbackOAD-FB25% FBDamper feedbackFilter differential pressureFLT-DP0.34 in.wcFilter pressureSupply-fan commandSF-CMDONFan commandSupply-fan proofSF-STSONFan proofFan speed feedbackSF-SPD-FB72% FBDrive feedbackHeating-valve commandHTG-VLV0% CMDHeating commandCooling-valve commandCLG-VLV28% CMDCooling commandHeating-valve feedbackHTG-VLV-FB0% FBHeating feedbackCooling-valve feedbackCLG-VLV-FB28% FBCooling feedbackSupply air temperature (SAT)DAT55.3°FSupply airMeasured supply airflowSA-CFM12000 cfmSupply airflow
Occupancy
Occupied
Supply air setpoint
55.0 °F
Duct static
1.36 in.w.c.
VFD command
72%
VFD feedback
72%
Air pathCoolingHeatingMismatch / safety

Read command, proof, and response. Select equipment or a point tag to inspect. Motion shows proven operation; it is not a calibrated flow or speed scale.

FAN COMMANDONINDEPENDENT PROOFONSUPPLY AIR (SAT)55.3°FMEASURED AIRFLOW12000 cfm
AHU SYSTEM BOUNDARYSupply duct continues to terminal equipment

VAV boxes, reheat coils, fan-powered boxes, diffusers, and fan-coil units have their own sequences and points. They are not compressed into the AHU graphic.

Open the separate fan-coil-unit lab →
REMOTE DEMAND SIGNAL · NOT IN AHU AIR PATH72.2°F zone · 72.0°F SP

+0.2°F error · CO₂ 710 ppm. These representative values influence AHU demand but belong to a downstream zone system.

Field note: Fan command and proof agree; temperatures, damper feedback, filter pressure, and outputs are stable.

DISCHARGE AIR55.3°FSetpoint: 55.0°F
RETURN AIR71.6°FRA–DA ΔT 16.3°F · MAT 73.2°F
DUCT STATIC1.36in. w.c. · SP 1.35
SUPPLY AIRFLOW12000 cfm100% design · fan 72%
ACTIVE ALARMS0Normal
Case briefTake over the building before the first complaint

Fictional training call · Office building · seasonal controls handover

Customer report

“Everything seems comfortable today. Can you document what normal operation looks like before our regular technician leaves?”

You inherit AHU-02 with an approved point list and a stable occupied run, but no useful operating baseline in the service log.

EVIDENCE-BASED TECHNICIAN CHALLENGE · CASE 0

Establish a normal operating snapshot before troubleshooting any complaint.

5 graded decisions
Supporting evidence Select only the three facts that prove the diagnosis.
Diagnostic confidence
Confidence records your judgment; it does not add points.