Skip to workspace
BAS Bridge
System explorer

Central plant

BLR-01 Hot-water boiler

Establishing circulation
SEQUENCE CLOCK 0s

Boiler, separation, and heating circuit

BLR-01 · Condensing hot-water plantDedicated boiler loop + distribution loopBURNER OFF
Equipment cutaway · select a point to inspect
BLR-01 hot-water boiler, pumps, hydraulic separator, and heating circuitOriginal schematic cutaway of a condensing boiler with monitored gas train, heat exchanger, flue and air intake. Separate boiler and distribution pumps connect through a hydraulic separator. Expansion tank connects upstream of the distribution pump. The burner is off. Select a labeled point to open its inspector. Gas safety and ignition remain under the local boiler controller.HEAT SOURCE → HYDRAULIC SEPARATION → HEATING LOADFICTIONAL TRAINING PLANT · NOT AN INSTALLATION DRAWINGBLR-01 / LOCAL CONTROLSTANDBYBLR-01 · STAINLESS FIRETUBE CUTAWAYAIR INTAKEFLUE TO OUTDOORSGAS · OEM SAFETY TRAINBAS READBACK ONLYRELIEF TOSAFE DISCHARGETRAP → NEUTRALIZER → DRAINHS-1AIR VENTHYDRAULIC SEPARATOREXPANSION TANKPUMP SUCTIONFILL / BACKFLOWBP-1 · BOILER PUMPSP-1 · SYSTEM PUMPAHU / ZONE HEATING LOADHEATING-WATER SUPPLY →← HEATING-WATER RETURNOutdoor air temperatureAIOAT35.0 °FFlue temperatureAIFLUE-T109.8 °FAccepted heating supply targetAVHWS-SP140.0 °FSystem heating-water supplyAIHWS-T118.8 °FRemote heating differential pressureAISYS-DP0.0 psiBoiler leaving-water sensorAIBLR-LWT118.8 °FLocal firing-rate readbackAIFIRE-RATE0 %Local flame-proven statusBIFLAME-STSOFFBoiler pump run proofBIBP-STSNOT PROVENDistribution pump run proofBISP-STSNOT PROVENMeasured boiler water flowAIBLR-FLOW0.0 gpmBoiler entering-water sensorAIBLR-EWT118.8 °FBoiler water temperature riseAVBLR-DT0.0 °FHeating system static pressureAISYS-P22.0 psiBoiler branch valve positionAIIV-FB0 %System heating-water returnAIHWR-T118.8 °FEffective heating demandAVHTG-LOAD60 %Plant alarm summaryBIBLR-ALMNORMALSelectable point tags show simulated measurements. Blue/red identify return/supply; they do not specify safe touch temperatures.
Heating-water supplyHeating-water returnGas train, readback only
Read command → proof → flow → thermal response. Pump rotation follows motor proof; pipe motion follows measured circuit flow. Motion is illustrative, not a flow-rate scale. Ignition, fuel valves, purge, low-water cutoff, and temperature limits belong to the local boiler safety controller. The drawing is an original teaching schematic; equipment details and available network points vary by model.

The branch valve and pumps are requested. Fuel remains closed until motor proof, valve position, measured boiler flow, and distribution proof are satisfactory.

System supply / target118.8 / 140 °FIndependent supply sensor / accepted reset target
Boiler water flow0 gpmFlow is not proven; fuel remains closed
Local firing rate0 %OEM readback, bounded by the BAS ceiling and local safeties
Useful water-side heat0 kBtu/hSimplified plain-water flow × ΔT heat transfer
Current service callBefore the school doors open

Follow the plant from a heat request to proven flame and useful heat delivery.

Alarms0Open training →
Model scope and assumptions

A fictional commercial gas-fired, stainless firetube hot-water boiler with a dedicated boiler pump, hydraulic separator, variable-speed distribution pump, outdoor reset, and local combustion controller. This is a learning model, not a manufacturer-specific controller or equipment selection tool.

Nominal 1,000 kBtu/h input; example 60 gpm boiler circuit; separate variable-flow heating distribution. All temperatures, pressure targets, capacities, delays, and alarm thresholds in the simulator are bounded teaching assumptions. Use the exact installed model's approved piping, flow ranges, gas specification, safety sequence, and point map for real work.

Run or advance the sequence to observe the requested stage. Changing the case retains your operator commands.

Sequence time is accelerated and illustrative; elapsed seconds are not OEM purge, restart, or safety timer settings.

Case briefBefore the school doors open

Fictional training call · Elementary school heating plant

Customer report

“The custodian wants to know whether the heating plant is ready for the morning arrival.”

You are checking the normal occupied warm-up sequence with the custodian before classrooms fill.

SERVICE EVIDENCE

Prove the boundary before changing parts.

  • Commands, motor proof, and actual flow are separate signals.
  • Watch outdoor reset, leaving-water response, distribution pressure, and flame readback.

WORKING RULES

Keep supervisory control and equipment protection separate.

  • BAS enable is a request; the local boiler controller and independent safety devices own fuel admission, ignition, purge, flame proving, and lockouts.
  • Command → motor proof → measured water flow → temperature response are different pieces of evidence. No single one proves the others.
  • Hydraulic separation decouples the boiler and distribution flow rates. An operating boiler pump does not prove that remote coils receive water.
  • Outdoor reset lowers the requested water temperature as weather warms. The target must remain compatible with the heating coils and approved boiler limits.
  • For plain water near ordinary heating conditions, approximate useful heat in kBtu/h ≈ 0.5 × gpm × water ΔT in °F. Glycol, temperature, and measurement error change the factor.
  • Lower return temperature can improve condensing potential. The 130 °F lab indicator is a teaching approximation, not a universal dew point or promised efficiency.
  • Alarm acknowledgment records an operator response. It never repairs a fault, clears an active condition, or overrides a local safety lockout.
  • Network points are model-specific. Confirm mapping, units, access, status meaning, freshness, and commissioned fallback at the actual local controller.

MANUFACTURER RESEARCH

Read the actual equipment literature.

Lochinvar CREST / Hellcat Modbus and BACnet instructions, Rev X ↗

Pages 10–11 and 18–20: network point families and read/write distinctions; pages 35–37: BAS unit-operation scope. Available points and signal polarity vary by model; lab IDs are semantic aliases, not wire addresses.

Lochinvar CREST service manual, Rev X ↗

Fault descriptions and local lockout/recovery context. The lab does not reproduce a specific controller's fault numbers or reset procedure.

Weil-McLain SVF 500/600 boiler manual — hydronic piping ↗

Pages 19–26: example boiler/system circulation, separation, valves, expansion, air elimination, fill, and relief components. Original lab drawing is schematic and does not replace an approved installation design.

Weil-McLain SVF 500/600 boiler manual — sequence ↗

Pages 84–87: standby, pre-purge, ignition, flame-proven modulation, post-purge, outdoor reset, and remote target context. Lab times are accelerated teaching values.

AERCO Edge controller communication manual ↗

Integrator point-list examples include inlet/outlet/exhaust temperature, flame strength, firing rate, valve state, operating state, hours, and cycles. Signal units and scaling are device-specific.

AERCO Control System plant-management overview ↗

Separates supervisory multi-boiler coordination and BAS monitoring from individual boiler operation. The lab represents a single active boiler branch.