Skip to workspace
BAS Bridge
System explorer

Fan-coil alarms

Read what happened, prove the cause, and distinguish acknowledgment from recovery.

Alarm drill scope

These are separate fictional fault drills. Values, alarm delays, priorities, and reset rules are teaching examples, not universal OEM settings. “Correct simulated condition” records an assumed repair in this exercise; it does not command equipment or authorize a field reset.

EVENT CLOCK 0
ACTIVE CONDITIONS2Fault still present
UNACKNOWLEDGED2Operator response outstanding
RESET REQUIRED0Condition clear, latch held
RECORDED EVENTS1This page’s training session

CURRENT DRILL

Warm room: valve mismatch and space deviation

Resolve source alarms first and verify downstream symptoms separately. A hidden or acknowledged row does not establish equipment recovery.

Priority / alarmEquipmentObserved atConditionAcknowledgmentLatchEvent
Highfcu-cooling-valveFan-coil—ACTIVEUNACKNOWLEDGEDClear#01 occurrence
Mediumfcu-room-highFan-coil—ACTIVEUNACKNOWLEDGEDClear#01 occurrence

EVENT JOURNAL

Keep the order of events.

Event numbers show action order. Times are local browser observations of the exercise. Records stay on this page until it reloads; no live alarm database is connected.

  1. #0 · —Scenario loaded: Warm room: valve mismatch and space deviation. Alarm conditions injected in the training workspace.

Read the alarm lifecycle.

01

Active condition

The fault condition remains true. Acknowledgment records an operator response and leaves the condition unchanged.

02

Returned to normal

The initiating condition is clear. Check independent proof and the process response before claiming recovery.

03

Latch / reset

A latching protection stays held after the condition clears. Its actual reset location, permissions, and restart procedure are equipment-specific.

PRIMARY SOURCE CONTEXT

Match the installed controller and approved sequence.

Johnson Controls — Metasys System Activity ↗

Acknowledgement, annotations and retained alarm history. BAS Bridge uses a simplified original lifecycle.

Johnson Controls — BACnet alarm attributes ↗

Delay, deadband and distinct alarm transitions; exact platform and project settings vary.

Trane — Guideline 36 Engineers Newsletter ↗

AHU diagnostics and source/dependent fault context. Original lab values do not claim Guideline 36 conformance.

Trane — Tracer AH.540 point diagram ↗

Historical component and point vocabulary for AHU commands, proofs, temperatures and protective inputs; not current product defaults.

Siemens — Ventilation application guide ↗

Airside coordination, air-quality inputs and flow-aware filter monitoring. Exercise thresholds are fictional.

Johnson Controls — Fan-coil condensate alarm ↗

The described application disables cooling; whole-unit shutdown is selectable. The lab declares its own fan-off response.

Danfoss — ERC refrigeration controller features ↗

Temperature, door, sensor and external alarm families; defrost and fan-delay operating context, not copied parameter settings.

Danfoss — KP and KPI pressure switches ↗

Manual and automatic reset variants and pressure-dependent reset permission. No field pressure setting is prescribed.