Skip to workspace
BAS Bridge
System explorer
Work order AHU-04

Free cooling is requested, but mixed air stays warm

Air-handling unit · Airside systems · Intermediate

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The economizer is enabled on a cool day, yet mixed air remains close to return-air temperature. Decide what the damper feedback actually proves.

Equipment and operating sequence

Illustrative dry-bulb economizer: outdoor air is suitable, cooling is required, and low-temperature protection is inactive. Feedback measures the actuator's internal position, not damper-blade angle or outdoor airflow.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Outdoor air: 50°F; return air: 75°F; mixed air: 73°F.
  • Outdoor damper command: 90%; actuator feedback: 89%.
  • Supply airflow: 8,000 cfm; economizer mixed-air target: 55°F; no useful mixed-air response after 120 seconds.
  • Mixed-air and outdoor sensors pass independent reference checks.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.

Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Intake / mixing · case readings

Outdoor air Reading
50 °F
Return air Reading
75 °F
Mixed air Reading
73 °F
Outdoor damper Command
90 %
Actuator position Feedback
89 %

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Outdoor airReading · Intake / mixing50°F————
Return airReading · Intake / mixing75°F————
Mixed airReading · Intake / mixing73°F————
Outdoor damperCommand · Intake / mixing90%90———
Actuator positionFeedback · Intake / mixing89%—89——

Intake observations

  • Outdoor air: 50°F; return air: 75°F; mixed air: 73°F.
  • Outdoor damper command: 90%; actuator feedback: 89%.
  • Supply airflow: 8,000 cfm; economizer mixed-air target: 55°F; no useful mixed-air response after 120 seconds.
  • Mixed-air and outdoor sensors pass independent reference checks.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
AHUSupply airflow: 8,000 cfm; economizer mixed-air target: 55°F; no useful mixed-air response after 120 seconds.Intake record

Field mentor