Work order AHU-07

Air warms up after it leaves the cooling coil

Air-handling unit · Hydronic systems · Intermediate

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The cooling coil produces cold air, but the final supply temperature is too warm. Investigate the energy added between the two measurement locations.

Equipment and operating sequence

Illustrative AHU has a cooling coil followed by a hot-water heating coil; fan heat is accounted for in the supplied normal baseline. Dehumidification/reheat mode is disabled by the documented sequence. Supply airflow is 2,000 cfm in this case.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Cooling-coil leaving air: 54°F; final supply air: 64°F; supply target: 55°F.
  • Heating-valve command: 0%; actuator feedback: 0%; heating request: false.
  • Hot-water inlet: 140°F; independent heating-coil flow: 0.8 gpm.
  • Both air-temperature sensors agree with references; normal downstream fan heat adds approximately 1°F.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.

Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Coils and valves · case readings

Cooling-coil leaving air Reading
54 °F
Heating valve Command
0 %
Actuator position Feedback
0 %
Heating-coil flow Reading
0.8 gpm

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Cooling-coil leaving airReading · Coils and valves54°F————
Final supply airReading · Duct / zones64°F————
Heating valveCommand · Coils and valves0%0———
Actuator positionFeedback · Coils and valves0%—0——
Heating-coil flowReading · Coils and valves0.8gpm————

Intake observations

  • Cooling-coil leaving air: 54°F; final supply air: 64°F; supply target: 55°F.
  • Heating-valve command: 0%; actuator feedback: 0%; heating request: false.
  • Hot-water inlet: 140°F; independent heating-coil flow: 0.8 gpm.
  • Both air-temperature sensors agree with references; normal downstream fan heat adds approximately 1°F.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.