Work order AHU-09

The occupied schedule is active, but the fan output remains off

Air-handling unit · Controls and communications · Advanced

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The schedule and automatic sequence request operation, yet the final command to the fan remains off. Find where the request loses authority.

Equipment and operating sequence

Illustrative commandable output: lower numbered active priority wins. Normal control writes at priority 16, and a non-safety maintenance override may write at priority 8. Life-safety and hardware interlocks are separate and satisfied.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Schedule: occupied; automatic sequence fan request: ON.
  • Effective fan output: OFF; drive remote mode: enabled; drive fault: none.
  • All required start permissives: satisfied; no output wiring fault indicated.
  • The AHU ran normally before a maintenance visit; point timestamps are current.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.

Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.

Beckhoff BACnet documentation: Command prioritization ↗
Priority arrays, effective present value and relinquishing a command by writing NULL at its priority.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Duct / zones · case readings

Occupied schedule Status
Occupied

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Occupied scheduleStatus · Duct / zonesOccupied———Occupied—
Automatic fan requestCommand · Supply fanOn—On———
Effective fan outputCommand · Supply fanOff—Off———
Drive remote modeStatus · Supply fanEnabled———Enabled—

Intake observations

  • Schedule: occupied; automatic sequence fan request: ON.
  • Effective fan output: OFF; drive remote mode: enabled; drive fault: none.
  • All required start permissives: satisfied; no output wiring fault indicated.
  • The AHU ran normally before a maintenance visit; point timestamps are current.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
AHUEffective fan output: OFF; drive remote mode: enabled; drive fault: none.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.