Skip to workspace
BAS Bridge
System explorer
Work order AHU-10

One zone keeps the entire AHU at high pressure

Air-handling unit · Airside systems · Advanced

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Most zones are satisfied, but duct-pressure reset remains at its upper limit. Investigate the persistent request before changing the AHU pressure limit.

Equipment and operating sequence

Illustrative trim-and-respond reset uses terminal airflow shortfall and damper position. VAV-12 was recently reconfigured; its documented airflow conversion is Q = K√ΔP, with consistent units and a commissioned K available. VAV-12's documented occupied minimum airflow is 700 cfm for this exercise, so its active target remains 700 cfm when no additional cooling is needed.

The connected training building uses VAV-01 to represent the terminal identified as VAV-12 in the dispatch record.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Duct-static target: maximum permitted 2.0 in. w.c.; measured static: 2.0 in. w.c.
  • Eleven VAV boxes are satisfied with dampers below 40%.
  • VAV-12 reports 300 cfm against a 700-cfm target, damper 100%, and persistent pressure requests.
  • The AHU has no fan alarm; VAV-12's zone is cooler than its setpoint.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.

Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Supply fan · case readings

Duct static Reading
2.0 in. w.c.
Duct static target Setpoint
2.0 in. w.c.

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Duct staticReading · Supply fan2.0in. w.c.————
Duct static targetSetpoint · Supply fan2.0in. w.c.————
VAV-12 airflowFeedback · Duct / zones300cfm—300——
VAV-12 airflow targetSetpoint · Duct / zones700cfm————

Intake observations

  • Duct-static target: maximum permitted 2.0 in. w.c.; measured static: 2.0 in. w.c.
  • Eleven VAV boxes are satisfied with dampers below 40%.
  • VAV-12 reports 300 cfm against a 700-cfm target, damper 100%, and persistent pressure requests.
  • The AHU has no fan alarm; VAV-12's zone is cooler than its setpoint.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
AHUThe AHU has no fan alarm; VAV-12's zone is cooler than its setpoint.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor