Work order AHU-12

The office wing stays cold during morning warm-up

Air-handling unit · Hydronic systems · Intermediate

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The office manager feels air moving at the diffusers, but the wing is still cold. The plant operator reports that the heating pump is running. Find where heat delivery stops.

Equipment and operating sequence

AHU-01 serves this wing. During this occupied warm-up exercise its automatic supply air target is 75°F. The chilled-water plant is off for the season. The heating coil has a modulating control valve and separate manual isolation valves.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • At dispatch the office was 63°F, compared with its occupied target of 72°F.
  • The supply air sensor read 61°F against a 75°F warm-up target. The supply fan had run for three minutes.
  • The heating valve command and actuator feedback both read 100%.
  • The heating pump showed run proof. Other areas on the same header were receiving heat.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Duct / zones · case readings

Office temperature Reading
63 °F
Supply air temperature Reading
61 °F
Supply air target Setpoint
75 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Office temperatureReading · Duct / zones63°F————
Supply air temperatureReading · Duct / zones61°F————
Supply air targetSetpoint · Duct / zones75°F————
Heating valve commandCommand · Coils and valves100%100———
Heating actuator positionFeedback · Coils and valves100%—100——
Plant pump run proofFeedback · Coils and valvesOn——On——

Intake observations

  • At dispatch the office was 63°F, compared with its occupied target of 72°F.
  • The supply air sensor read 61°F against a 75°F warm-up target. The supply fan had run for three minutes.
  • The heating valve command and actuator feedback both read 100%.
  • The heating pump showed run proof. Other areas on the same header were receiving heat.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.