Burner repeatedly starts and stops
Boiler · Sequences of operation · Intermediate
Customer complaint
Trend data shows many short burner cycles during steady heating demand. Identify what changed before recommending additional equipment.
Equipment and operating sequence
Illustrative on/off plant with adequate connected water volume. Approved normal control starts at 140°F and stops at 150°F; all OEM limits remain independent.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Heat demand remains ON for 30 minutes.
- Burner cycles approximately every 50 seconds, stopping near 150°F and restarting near 149°F.
- Water flow and connected zone count match a previously stable operating period.
- No local high-limit trip or flame-loss event appears in the event log.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Boiler · case readings
- Heat demand Status
- On
- Observed cycle period Reading
- ≈50 s
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Heat demand | Status · Boiler | On | — | — | — | On | — |
| Observed cycle period | Reading · Boiler | ≈50 | s | — | — | — | — |
| Stop temperature | Reading · Supply header | ≈150 | °F | — | — | — | — |
| Restart temperature | Reading · Supply header | ≈149 | °F | — | — | — | — |
Intake observations
- Heat demand remains ON for 30 minutes.
- Burner cycles approximately every 50 seconds, stopping near 150°F and restarting near 149°F.
- Water flow and connected zone count match a previously stable operating period.
- No local high-limit trip or flame-loss event appears in the event log.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Boiler | No local high-limit trip or flame-loss event appears in the event log. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Boiler | Heat demand remains ON for 30 minutes. | Intake record |
| Boiler | Burner cycles approximately every 50 seconds, stopping near 150°F and restarting near 149°F. | Intake record |
| Boiler | Water flow and connected zone count match a previously stable operating period. | Intake record |