Work order BL-08

The boiler stays idle during the morning heat call

Boiler · Electrical · Advanced

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The plant operator sees a heat request and a common alarm, but the building is cold. Establish where the request stops and what a boiler technician needs to investigate.

Equipment and operating sequence

The boiler receives a remote enable. Its local controller supervises the burner and reports runtime and a common alarm to the BAS.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • BMS demand and the locally received external request are ON.
  • The burner runtime contact is OFF.
  • The summary alarm is active. All displayed status timestamps are current.
  • The work order includes no technician inspection of the boiler.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Boiler · case readings

BMS heat demand Command
On
Received external enable Feedback
On
Burner runtime Feedback
Off
Summary alarm Status
Active

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
BMS heat demandCommand · BoilerOn—On———
Received external enableFeedback · BoilerOn——On——
Burner runtimeFeedback · BoilerOff——Off——
Summary alarmStatus · BoilerActive———Active—

Intake observations

  • BMS demand and the locally received external request are ON.
  • The burner runtime contact is OFF.
  • The summary alarm is active. All displayed status timestamps are current.
  • The work order includes no technician inspection of the boiler.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
BoilerThe burner runtime contact is OFF.Intake recordUnreportedUnreportedUnreported
BoilerThe summary alarm is active. All displayed status timestamps are current.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor