The boiler stays idle during the morning heat call
Boiler · Electrical · Advanced
Customer complaint
The plant operator sees a heat request and a common alarm, but the building is cold. Establish where the request stops and what a boiler technician needs to investigate.
Equipment and operating sequence
The boiler receives a remote enable. Its local controller supervises the burner and reports runtime and a common alarm to the BAS.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- BMS demand and the locally received external request are ON.
- The burner runtime contact is OFF.
- The summary alarm is active. All displayed status timestamps are current.
- The work order includes no technician inspection of the boiler.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Boiler · case readings
- BMS heat demand Command
- On
- Received external enable Feedback
- On
- Burner runtime Feedback
- Off
- Summary alarm Status
- Active
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| BMS heat demand | Command · Boiler | On | — | On | — | — | — |
| Received external enable | Feedback · Boiler | On | — | — | On | — | — |
| Burner runtime | Feedback · Boiler | Off | — | — | Off | — | — |
| Summary alarm | Status · Boiler | Active | — | — | — | Active | — |
Intake observations
- BMS demand and the locally received external request are ON.
- The burner runtime contact is OFF.
- The summary alarm is active. All displayed status timestamps are current.
- The work order includes no technician inspection of the boiler.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Boiler | The burner runtime contact is OFF. | Intake record | Unreported | Unreported | Unreported |
| Boiler | The summary alarm is active. All displayed status timestamps are current. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.