Condenser-side permissive never arrives
Chiller · Sequences of operation · Foundation
Customer complaint
CHW flow is established, yet the machine remains unavailable to start. Determine why the condenser-water side cannot complete its sequence.
Equipment and operating sequence
Illustrative water-cooled chiller with a motorized CW isolation valve. The CW pump starts only after independent full-open proof; timeout is 60 seconds.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 09:10: evaporator flow 480 gpm, valid; CHW permissive TRUE.
- CW valve command OPEN for 90 seconds; open limit FALSE.
- CW pump command OFF; condenser flow 0 gpm; no pump fault.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator · case readings
- Evaporator flow Reading
- 480 gpm
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Evaporator flow | Reading · Evaporator | 480 | gpm | — | — | — | — |
| Condenser valve | Command · Condenser system | Open | — | Open | — | — | — |
| Valve open limit | Feedback · Condenser system | False | — | — | False | — | — |
| Condenser flow | Reading · Condenser system | 0 | gpm | — | — | — | — |
Intake observations
- 09:10: evaporator flow 480 gpm, valid; CHW permissive TRUE.
- CW valve command OPEN for 90 seconds; open limit FALSE.
- CW pump command OFF; condenser flow 0 gpm; no pump fault.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Chiller | CW pump command OFF; condenser flow 0 gpm; no pump fault. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.