Work order CH-06

High water flow with a small plant temperature rise

Chiller · Hydronic systems · Intermediate

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Operators suspect that the plant needs another chiller because flow is high. Use temperature and flow evidence to distinguish cooling load from unnecessary recirculation.

Equipment and operating sequence

Illustrative variable-primary water-only plant with a modulating minimum-flow bypass. Evaporator minimum is 150 gpm; measured coil flow is 200 gpm. The pump maintains the approved distribution-pressure target and coil demand is unchanged for the recovery comparison.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 10:30: evaporator flow 600 gpm; CHWS 44°F; mixed return 48°F.
  • Coil branch flow 200 gpm; coil return 56°F; readings independently checked.
  • Minimum-flow bypass command 0%; chiller load approximately 100 tons, below available capacity.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator · case readings

Evaporator flow Reading
600 gpm
CHWS Reading
44 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Evaporator flowReading · Evaporator600gpm————
CHWSReading · Evaporator44°F————
Mixed returnReading · CHW distribution48°F————
Bypass valveCommand · CHW distribution0%0———

Intake observations

  • 10:30: evaporator flow 600 gpm; CHWS 44°F; mixed return 48°F.
  • Coil branch flow 200 gpm; coil return 56°F; readings independently checked.
  • Minimum-flow bypass command 0%; chiller load approximately 100 tons, below available capacity.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor