Chilled water settles above the operator's requested target
Chiller · Controls and communications · Advanced
Customer complaint
The operator enters a colder CHW target, but leaving water remains stable at a warmer value. Trace which setpoint actually reaches the local controller.
Equipment and operating sequence
Illustrative integration with a BACnet commandable remote-setpoint object. Lower-numbered active priorities win; the normal optimization routine writes at priority 16. Local remote-control mode is enabled.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 12:10: normal routine requests 44°F; leaving water stable at 52°F.
- Local effective remote target 52°F; compressor 31%, no capacity limit or alarm.
- Communication is valid, timestamps advance, and independent temperature confirms 52°F.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Beckhoff BACnet documentation: Command prioritization ↗
Priority arrays, effective present value and relinquishing a command by writing NULL at its priority.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator · case readings
- Routine request Command
- 44 °F
- Leaving chilled water Reading
- 52 °F
- Effective remote target Setpoint
- 52 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Routine request | Command · Evaporator | 44 | °F | 44 | — | — | — |
| Leaving chilled water | Reading · Evaporator | 52 | °F | — | — | — | — |
| Effective remote target | Setpoint · Evaporator | 52 | °F | — | — | — | — |
| Compressor load | Reading · Compressor | 31 | % | — | — | — | — |
Intake observations
- 12:10: normal routine requests 44°F; leaving water stable at 52°F.
- Local effective remote target 52°F; compressor 31%, no capacity limit or alarm.
- Communication is valid, timestamps advance, and independent temperature confirms 52°F.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Chiller | Local effective remote target 52°F; compressor 31%, no capacity limit or alarm. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.