Work order CH-10

Chilled water settles above the operator's requested target

Chiller · Controls and communications · Advanced

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The operator enters a colder CHW target, but leaving water remains stable at a warmer value. Trace which setpoint actually reaches the local controller.

Equipment and operating sequence

Illustrative integration with a BACnet commandable remote-setpoint object. Lower-numbered active priorities win; the normal optimization routine writes at priority 16. Local remote-control mode is enabled.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 12:10: normal routine requests 44°F; leaving water stable at 52°F.
  • Local effective remote target 52°F; compressor 31%, no capacity limit or alarm.
  • Communication is valid, timestamps advance, and independent temperature confirms 52°F.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Beckhoff BACnet documentation: Command prioritization ↗
Priority arrays, effective present value and relinquishing a command by writing NULL at its priority.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator · case readings

Routine request Command
44 °F
Leaving chilled water Reading
52 °F
Effective remote target Setpoint
52 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Routine requestCommand · Evaporator44°F44———
Leaving chilled waterReading · Evaporator52°F————
Effective remote targetSetpoint · Evaporator52°F————
Compressor loadReading · Compressor31%————

Intake observations

  • 12:10: normal routine requests 44°F; leaving water stable at 52°F.
  • Local effective remote target 52°F; compressor 31%, no capacity limit or alarm.
  • Communication is valid, timestamps advance, and independent temperature confirms 52°F.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
ChillerLocal effective remote target 52°F; compressor 31%, no capacity limit or alarm.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.