Work order RF-02

Cold near the coil, warm across the box

Refrigeration system · Electrical · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Determine why a running refrigeration circuit does not distribute cooling through the space.

Equipment and operating sequence

Medium-temperature TXV cooler with two parallel evaporator fans. Both should run during established refrigeration; defrost and fan delay are inactive.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Box: 44°F against 35°F setpoint; evaporator inlet air: 43°F.
  • Fan relay command: ON; shared relay feedback: ON.
  • One discharge-air region: 28°F; far-box logger: 46°F.
  • Evaporator face inspection snapshot shows little frost; compressor is running.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.

Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator / box · case readings

Box temperature Reading
44 °F
Box target Setpoint
35 °F
Fan relay Command
On
Shared relay Feedback
On

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Box temperatureReading · Evaporator / box44°F————
Box targetSetpoint · Evaporator / box35°F————
Fan relayCommand · Evaporator / boxOn—On———
Shared relayFeedback · Evaporator / boxOn——On——
CompressorStatus · CompressorRunning———Running—

Intake observations

  • Box: 44°F against 35°F setpoint; evaporator inlet air: 43°F.
  • Fan relay command: ON; shared relay feedback: ON.
  • One discharge-air region: 28°F; far-box logger: 46°F.
  • Evaporator face inspection snapshot shows little frost; compressor is running.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.