Work order RF-05

Cooling weakens on a mild afternoon

Refrigeration system · Refrigeration · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Determine what changed in condenser heat rejection before selecting a refrigerant-side repair.

Equipment and operating sequence

Air-cooled R-134a TXV cooler. Stable snapshots have comparable box load and 80°F condenser-entering air; no low-ambient head-pressure mode is active.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Box: 43°F against 35°F target; continuous cooling demand.
  • Condensing saturation temperature: 130°F versus 105°F in the matched normal snapshot.
  • Both condenser fans are commanded on; no fresh high-pressure trip is shown.
  • Condenser-entering air: 80°F at the coil; discharge-air temperature is elevated.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.

Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator / box · case readings

Box temperature Reading
43 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Box temperatureReading · Evaporator / box43°F————
Condensing saturationReading · Condenser130°F————
Condenser fansCommand · CondenserOn—On———
Condenser entering airReading · Condenser80°F————

Intake observations

  • Box: 43°F against 35°F target; continuous cooling demand.
  • Condensing saturation temperature: 130°F versus 105°F in the matched normal snapshot.
  • Both condenser fans are commanded on; no fresh high-pressure trip is shown.
  • Condenser-entering air: 80°F at the coil; discharge-air temperature is elevated.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
RefrigerationBoth condenser fans are commanded on; no fresh high-pressure trip is shown.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
RefrigerationCondensing saturation temperature: 130°F versus 105°F in the matched normal snapshot.Intake record