The evaporator is starved despite available liquid
Refrigeration system · Refrigeration · Advanced
Customer complaint
Locate the loss of liquid-delivery pressure without treating starvation as proof of low charge.
Equipment and operating sequence
R-134a TXV cooler with receiver and accessible instrumented liquid-line sections in the teaching model. All pressure-drop observations are pre-recorded service results, not instructions to add field taps.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Evaporator-outlet saturation: 10°F; tube: 40°F, giving 30°F superheat.
- The receiver-outlet snapshot confirms subcooled liquid at that location.
- Box: 45°F with stable cooling demand and normal verified evaporator airflow.
- Liquid temperature falls along one section between receiver and TXV; its location is initially hidden.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Evaporator saturation Reading
- 10 °F
- Outlet tube Reading
- 40 °F
- Superheat Reading
- 30 °F
- Box temperature Reading
- 45 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Evaporator saturation | Reading · Evaporator / box | 10 | °F | — | — | — | — |
| Outlet tube | Reading · Evaporator / box | 40 | °F | — | — | — | — |
| Superheat | Reading · Evaporator / box | 30 | °F | — | — | — | — |
| Box temperature | Reading · Evaporator / box | 45 | °F | — | — | — | — |
Intake observations
- Evaporator-outlet saturation: 10°F; tube: 40°F, giving 30°F superheat.
- The receiver-outlet snapshot confirms subcooled liquid at that location.
- Box: 45°F with stable cooling demand and normal verified evaporator airflow.
- Liquid temperature falls along one section between receiver and TXV; its location is initially hidden.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.