The evaporator is starved despite available liquid

Refrigeration system · Refrigeration · Advanced

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Locate the loss of liquid-delivery pressure without treating starvation as proof of low charge.

Equipment and operating sequence

R-134a TXV cooler with receiver and accessible instrumented liquid-line sections in the teaching model. All pressure-drop observations are pre-recorded service results, not instructions to add field taps.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Evaporator-outlet saturation: 10°F; tube: 40°F, giving 30°F superheat.
  • The receiver-outlet snapshot confirms subcooled liquid at that location.
  • Box: 45°F with stable cooling demand and normal verified evaporator airflow.
  • Liquid temperature falls along one section between receiver and TXV; its location is initially hidden.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.

Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator / box · case readings

Evaporator saturation Reading
10 °F
Outlet tube Reading
40 °F
Superheat Reading
30 °F
Box temperature Reading
45 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Evaporator saturationReading · Evaporator / box10°F————
Outlet tubeReading · Evaporator / box40°F————
SuperheatReading · Evaporator / box30°F————
Box temperatureReading · Evaporator / box45°F————

Intake observations

  • Evaporator-outlet saturation: 10°F; tube: 40°F, giving 30°F superheat.
  • The receiver-outlet snapshot confirms subcooled liquid at that location.
  • Box: 45°F with stable cooling demand and normal verified evaporator airflow.
  • Liquid temperature falls along one section between receiver and TXV; its location is initially hidden.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.