Air handling system

AHU-01 Supply air handler

Fan proven
Simulation settings

Air path and operating points

Occupied cooling

FAN → COILSSelectedDAT 56.4°FRead-only

Select Enlarge detail to inspect readings at full size.

AHU-01 equipment and live training pointsAir-handling unit cutaway with fan before the coil. Fan command ON; fan proof ON. Read command, proof, and response. Point values are supplied by the training simulation. A dash denotes unavailable data. Motion indicates proof, not a calibrated speed or flow measurement. Select a point tag to inspect its details.OUTDOOR + RETURN AIR → CONDITIONING → SUPPLYBLOW-THROUGHSELECT ANY POINT TO INSPECTMIXING BOXFILTER BANKSUPPLY FANHEATING COILCOOLING COILSUPPLY AIROutdoor-air temperatureOAT95.4°FOutdoor airReturn-air temperatureRAT77.8°FReturn airOutdoor-air damper commandOAD-CMD25% CMDDamper commandMixed-air temperatureMAT80.0°FMixed airOutdoor-air damper feedbackOAD-FB25% FBDamper feedbackFilter differential pressureFLT-DP0.34 in.wcFilter pressureSupply-fan commandSF-CMDONFan commandSupply-fan proofSF-STSONFan proofFan speed feedbackSF-SPD-FB82% FBDrive feedbackHeating-valve commandHTG-VLV0% CMDHeating commandCooling-valve commandCLG-VLV92% CMDCooling commandHeating-valve feedbackHTG-VLV-FB0% FBHeating feedbackCooling-valve feedbackCLG-VLV-FB92% FBCooling feedbackSupply air temperature (SAT)DAT56.4°FSupply airMeasured supply airflowSA-CFM12000 cfmSupply airflow
Occupancy
Occupied
Supply air setpoint
55.0 °F
Duct static
1.31 in.w.c.
VFD command
82%
VFD feedback
82%
Air pathCoolingHeatingMismatch / safety

Read command, proof, and response. Select equipment or a point tag to inspect. Motion shows proven operation; it is not a calibrated flow or speed scale.

FAN COMMANDONINDEPENDENT PROOFONSUPPLY AIR (SAT)56.4°FMEASURED AIRFLOW12000 cfm
AHU SYSTEM BOUNDARYSupply duct continues to terminal equipment

VAV boxes, reheat coils, fan-powered boxes, diffusers, and fan-coil units have their own sequences and points. They are not compressed into the AHU graphic.

Open the separate fan-coil-unit lab →
REMOTE DEMAND SIGNAL · NOT IN AHU AIR PATH78.4°F zone · 72.0°F SP

+6.4°F error · CO₂ 710 ppm. These representative values influence AHU demand but belong to a downstream zone system.

Field note: Outdoor air is hot. AHU discharge air is near setpoint, the fan is proven, and the cooling valve is near full open.

DISCHARGE AIR56.4°FSetpoint: 55.0°F
RETURN AIR77.8°FRA–DA ΔT 21.4°F · MAT 80.0°F
DUCT STATIC1.31in. w.c. · SP 1.35
SUPPLY AIRFLOW12000 cfm100% design · fan 82%
ACTIVE ALARMS1Zone temp high
Case briefThe west-side offices warm up every afternoon

Fictional training call · Commercial office · hot afternoon comfort call

Customer report

“It feels fine in the morning, but by late afternoon everyone on this side is warm. Is the air handler broken?”

Occupants want an immediate controls adjustment while the AHU is delivering cool air and the cooling output is already high.

EVIDENCE-BASED TECHNICIAN CHALLENGE · CASE 1

Several occupants report warm rooms late in the afternoon. Decide whether AHU-01 has failed.

5 graded decisions
Supporting evidence Select only the three facts that prove the diagnosis.
Diagnostic confidence
Confidence records your judgment; it does not add points.