Level 3 · Practical exam

The morning operating complaint

Identify who controls the equipment, use time-aligned trends to locate the first change, and prove recovery in the occupied office.

Practical evidence

Your verified practical records are attached below. The signed report and an independent knowledge pass are both required. The simulator verifies the practical checks. Your written conclusion is retained for review.

Practical outstanding.

Independent transfer assessment

Pass at 80%. Every safety item must also pass.

1. At 07:00 the schedule switches to Occupied. An old higher-priority command still owns the fan. What does the schedule change establish?
2. A 15-second trend interval covers six consecutive gaps between samples. How much time elapsed?
3. How do you close the operator test? · Required for safety
4. Only the perimeter is cold. Hot-water supply is available at the plant. What should you compare at the affected coil?
5. The airflow chart stops updating at 07:02. A high zone temperature alarm arrives at 07:18. What evidence can establish the order of physical events?