Lesson · 18 min

Command versus proof

Trace what the BAS asked for, what left the controller, what moved in the field and whether the process responded.

Follow the signal chain

Select a stage to inspect it. Every arrow marks a boundary that can fail independently.

Supply fan command and independent proofScroll the diagram to follow the signal.
Controller command, stopped fan, and independent proofThe occupied request is valid and the fan command is ON. Twenty-four volts AC reaches the starter. The fan is stopped, the independent fan-status input is OFF, and airflow is zero CFM. The return path represents an independent status input to the controller. Select the text stages below to explore what each observation establishes.REQUESTOccupiedCONTROLLERSF-CMD ONBAS / SOFTWARE INTENT24 VACSTARTERPHYSICAL FAN / STOPPEDAIRFLOW0 CFMSTATUS INPUTSF-STS OFFINDEPENDENT PROOF RETURNS TO THE CONTROLLER

Command, electrical output, physical motion, reported status and process response are separate observations. The fan stays still because this example reports it stopped.

COMMAND

SF-CMD ON

The BAS program asks the output to turn on. This proves software intent only.

Comparing evidence

COMMAND ONLY

SF-CMD = ON

The program reached the binary output. You still do not know whether voltage left the controller, the starter pulled in, the motor rotated, or airflow developed.

Confidence: intent only
COMMAND + PROOF + PROCESS

ON · Proven · Airflow

The request, controller intent, independent status, and measured result agree. That is a defensible operating conclusion.

Confidence: corroborated

Where does this sequence stop?

Occupied request is valid. SF-CMD is ON. The controller relay is closed and 24 VAC reaches the starter input. The fan does not rotate, SF-STS is OFF, and airflow is zero.

✓ Occupied request: VALID✓ SF-CMD: ON✓ Controller relay: CLOSED✓ Starter input: 24 VAC! Fan rotation: STOPPED! SF-STS: OFF! Airflow: 0 CFM
Select the first unproven boundary

Knowledge check

Choose one answer for each question. A passing score is 3 of 4.

01The BAS shows a supply fan command of ON. What has been proven?
02The fan is visibly running, but SF-STS remains OFF. Where is the first unproven boundary?
03Which set is strongest evidence that a damper followed its command?
04A freeze safety is active while an operator tries to force the fan ON. What is the correct action?
0/4 answered

Apply it to a fan-proof case

Use the AHU simulator to identify the fault boundary, weigh the evidence and choose the next safe test.

Open fan-proof case →Open field tools →