Command versus proof
Trace what the BAS asked for, what left the controller, what moved in the field and whether the process responded.
Follow the signal chain
Select a stage to inspect it. Every arrow marks a boundary that can fail independently.
Command, electrical output, physical motion, reported status and process response are separate observations. The fan stays still because this example reports it stopped.
SF-CMD ON
The BAS program asks the output to turn on. This proves software intent only.
Comparing evidence
SF-CMD = ON
The program reached the binary output. You still do not know whether voltage left the controller, the starter pulled in, the motor rotated, or airflow developed.
Confidence: intent onlyON · Proven · Airflow
The request, controller intent, independent status, and measured result agree. That is a defensible operating conclusion.
Confidence: corroboratedWhere does this sequence stop?
Occupied request is valid. SF-CMD is ON. The controller relay is closed and 24 VAC reaches the starter input. The fan does not rotate, SF-STS is OFF, and airflow is zero.
Knowledge check
Choose one answer for each question. A passing score is 3 of 4.
Apply it to a fan-proof case
Use the AHU simulator to identify the fault boundary, weigh the evidence and choose the next safe test.
Open fan-proof case →Open field tools →