Lesson · 12 min
Trends and diagnostic evidence
Build a useful trend bundle, preserve time context, and choose an observation that distinguishes competing explanations.
Trend a relationship, not an isolated number
Begin with a question: is the system following its sequence under this operating condition? Record the measured variable, target, command, available feedback, and relevant modes together. PNNL's re-tuning guides demonstrate this with groups of related points and examples of expected and abnormal operation. A temperature trace alone usually leaves too much of the control chain unexplained.
Give every point a clear identity
Record equipment, point meaning, units, source, and timestamps. BACnet distinguishes an object's identity from its readable name, and objects expose properties such as their present value. A friendly label can be ambiguous or incorrectly mapped. Confirm the actual source and engineering meaning before combining values from different controllers or trusting an apparent disagreement.
Choose a time scale that reveals the behavior
The interval must resolve the event you want to investigate. A coarse sample can miss short cycling or make two changing signals appear unrelated. Preserve gaps and stale periods instead of drawing them as normal operation. In an original training example, a two-minute cycle cannot be characterized reliably by taking one instantaneous sample every fifteen minutes. Compare startup, steady operation, and mode transitions.
Use the trend to direct the walkdown
A repeated mismatch suggests a question to investigate. It does not automatically identify a failed part. FEMP's re-tuning process combines data collection and analysis with a building walkdown, documented actions, and continued evaluation. State the observation, list the best-supported explanations, then select a physical or independent measurement that distinguishes them. After a change, compare equivalent operating conditions and preserve unresolved limitations.
Field exercise
Fictional exercise: a fan status trend is flat for four hours. What is the best next investigation?
Knowledge check
Answer all four questions. Pass the field exercise and at least three questions to complete this lesson.
Sources and scope
These original exercises draw on the sources below. For equipment settings and field actions, use the exact model, firmware, approved sequence and site procedure. Sources reviewed October 20, 2026.