Network troubleshooting guide

Localize an unavailable or stale value using the network riser, device identity, time and health of neighboring devices.

Observations that separate failure scopes

Observations that separate failure scopes
ObservationNext evidence
One point stale, other points on that controller freshCheck the exact object or register binding, polling or change reporting, quality and source timestamp.
One field controller missing from an otherwise healthy trunkCheck its local power and status, documented addressing, configuration changes and last successful communication.
Every downstream MS/TP controller missingCompare router status, a known local controller and the affected segment against the as-built bus. Verify physical trunk continuity and configured baud rate under authorized procedures.
Intermittent MS/TP errors after a device additionCompare MAC addresses on that segment, bus topology and documented termination/bias provisions. Match the manufacturer’s terminal designations and installation instructions.
IP controller locally reachable but supervisory values staleCompare IP address, subnet, expected path and BACnet network settings with the approved inventory. Local connectivity alone does not validate object bindings.
Modbus device responds but pressure is implausibleVerify serial settings or TCP unit mapping, function and register, address-base convention, signedness, byte/word order and numeric scaling against its published register map.

Field example

Three east-wing controllers share one router. Their supervisory values stopped at 15:23 while points behind a second router remain fresh. Observe local controller operation and router/trunk health before readdressing any individual controller.