Locate disagreement among the sampled condition, sensor element, transmitter, controller input and displayed units.

Common measurement patterns

Common measurement patterns
PatternA discriminating check
Constant offset at two stable pointsCo-locate a calibrated reference. Check placement, documented offset and wiring error before changing calibration.
Agreement at low end, growing error at high endInspect input/transmitter endpoints and exact element curve. Compare at another well-separated reference value.
RTD or thermistor jumps when the cable movesUnder verified isolation compare element and cable resistance separately. Check leads and terminations against the sensor documentation.
Duct static stays near zero while airflow changesCompare a manometer at the same taps. Inspect pinched or leaking lines, port assignment, range and displayed resolution.
CO₂ stays unusually low in a continuously occupied roomCompare an independent ppm reading at the same location, then check range, sampling location and how the specific sensor establishes its baseline.
Relative humidity disagrees at two locationsBring both sensors into the same air and compare temperature during stabilization. Temperature differences can explain a change in RH.

Field example

At 12 mA, a pressure transmitter and local gauge indicate 1.0 in. w.c. The controller shows 1.5. A correct midpoint electrical signal and independent reference move the investigation toward the input configuration.