Original module 12 assessment

Capstone training

Investigate three multi-system complaints. Collect independent witnesses, calculate a discrepancy, correct the supported cause and verify recovery.

Module examination

Pass at 80%.

Complete the three field investigations before submitting the capstone assessment.

1. A controller is observed at 09:10:30. Its last update was 09:09:45. How old is the sample?
2. After restoration, a water coil carries 9 gpm with 146°F entering and 132°F leaving. Calculate recovered heat using the training water approximation.
3. A repair restores fresh controller updates. Occupancy still fails to reach the air handler. Which observation closes the cross-system portion of the call?
4. What makes a convincing post-repair occupancy test?
5. Which result verifies the system-level effect?
6. A box reports 200 cfm. A calibrated hood measures 600 cfm. What is measured flow divided by reported flow?
7. Why collect a clean strainer baseline at the same branch flow?
8. Using 500 × gpm × ΔT for ordinary water in this exercise, what heat rate does 8 gpm at 15°F drop deliver?