One office keeps asking for more cooling
Air-handling unit · Sensors and instrumentation · Foundation
Customer complaint
An office reports feeling chilly while its VAV box requests maximum cooling. Determine which evidence should be trusted.
Equipment and operating sequence
Illustrative cooling-only occupied condition: zone cooling setpoint 74°F, heating inactive, AHU supply air 55°F. A representative zone sensor should agree with a colocated calibrated reference within this exercise's ±0.5°F tolerance.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Zone temperature: 79°F; cooling setpoint: 74°F.
- VAV airflow: 820 cfm; active airflow setpoint: 850 cfm.
- AHU supply air: 55°F; adjacent office temperatures: 73–75°F.
- Occupant reports feeling cold; zone value remains 78–79°F over 20 minutes.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Duct / zones · case readings
- Zone temperature Reading
- 79 °F
- Zone cooling target Setpoint
- 74 °F
- VAV airflow Feedback
- 820 cfm
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Zone temperature | Reading · Duct / zones | 79 | °F | — | — | — | — |
| Zone cooling target | Setpoint · Duct / zones | 74 | °F | — | — | — | — |
| VAV airflow | Feedback · Duct / zones | 820 | cfm | — | 820 | — | — |
| AHU supply air | Reading · Supply fan | 55 | °F | — | — | — | — |
Intake observations
- Zone temperature: 79°F; cooling setpoint: 74°F.
- VAV airflow: 820 cfm; active airflow setpoint: 850 cfm.
- AHU supply air: 55°F; adjacent office temperatures: 73–75°F.
- Occupant reports feeling cold; zone value remains 78–79°F over 20 minutes.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| AHU | Occupant reports feeling cold; zone value remains 78–79°F over 20 minutes. | Intake record |