The fan is working harder while airflow falls
Air-handling unit · Airside systems · Foundation
Customer complaint
Several zones are warm. The supply fan has reached its speed limit, but the AHU delivers less air than its recent commissioned baseline.
Equipment and operating sequence
Illustrative VAV AHU with a filter bank upstream of the fan. Reference readings are supplied at the same 8,000-cfm test airflow, eliminating airflow as the explanation for differing filter pressure drops.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Supply fan speed: 100%; duct static: 0.8 in. w.c.; active setpoint: 1.4 in. w.c.
- Current total airflow: 8,000 cfm; recent full-load baseline: 11,000 cfm.
- Several VAV dampers exceed 95% open; measured zone airflows are below their setpoints.
- Filter differential pressure: 1.1 in. w.c.; no fan-drive fault.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Supply fan · case readings
- Supply fan speed Reading
- 100 %
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Supply fan speed | Reading · Supply fan | 100 | % | — | — | — | — |
| Duct static pressure | Reading · Duct / zones | 0.8 | in. w.c. | — | — | — | — |
| Duct static target | Setpoint · Duct / zones | 1.4 | in. w.c. | — | — | — | — |
| Filter pressure drop | Reading · Intake / mixing | 1.1 | in. w.c. | — | — | — | — |
Intake observations
- Supply fan speed: 100%; duct static: 0.8 in. w.c.; active setpoint: 1.4 in. w.c.
- Current total airflow: 8,000 cfm; recent full-load baseline: 11,000 cfm.
- Several VAV dampers exceed 95% open; measured zone airflows are below their setpoints.
- Filter differential pressure: 1.1 in. w.c.; no fan-drive fault.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| AHU | Filter differential pressure: 1.1 in. w.c.; no fan-drive fault. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| AHU | Current total airflow: 8,000 cfm; recent full-load baseline: 11,000 cfm. | Intake record |