Morning heat request without burner operation
Boiler · Sequences of operation · Foundation
Customer complaint
Occupied rooms remain cool. Find where the heating request stops before recommending a repair.
Equipment and operating sequence
Illustrative single boiler: external heat enable is accepted only in Remote mode. Its own controller retains all startup and safety authority.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- At 06:10, occupied demand and BMS heat-enable command are ON; samples are current.
- System supply is 92°F against a 140°F target.
- Circulator is operating; independent water-flow indication is normal for this model.
- Burner runtime contact is OFF; local alarm contact is clear.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Boiler · case readings
- BMS enable Command
- On
- Burner runtime Feedback
- Off
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| BMS enable | Command · Boiler | On | — | On | — | — | — |
| System supply | Reading · Supply header | 92 | °F | — | — | — | — |
| Supply target | Setpoint · Supply header | 140 | °F | — | — | — | — |
| Burner runtime | Feedback · Boiler | Off | — | — | Off | — | — |
Intake observations
- At 06:10, occupied demand and BMS heat-enable command are ON; samples are current.
- System supply is 92°F against a 140°F target.
- Circulator is operating; independent water-flow indication is normal for this model.
- Burner runtime contact is OFF; local alarm contact is clear.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Boiler | Burner runtime contact is OFF; local alarm contact is clear. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.