Work order BL-01

Morning heat request without burner operation

Boiler · Sequences of operation · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Occupied rooms remain cool. Find where the heating request stops before recommending a repair.

Equipment and operating sequence

Illustrative single boiler: external heat enable is accepted only in Remote mode. Its own controller retains all startup and safety authority.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • At 06:10, occupied demand and BMS heat-enable command are ON; samples are current.
  • System supply is 92°F against a 140°F target.
  • Circulator is operating; independent water-flow indication is normal for this model.
  • Burner runtime contact is OFF; local alarm contact is clear.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Boiler · case readings

BMS enable Command
On
Burner runtime Feedback
Off

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
BMS enableCommand · BoilerOn—On———
System supplyReading · Supply header92°F————
Supply targetSetpoint · Supply header140°F————
Burner runtimeFeedback · BoilerOff——Off——

Intake observations

  • At 06:10, occupied demand and BMS heat-enable command are ON; samples are current.
  • System supply is 92°F against a 140°F target.
  • Circulator is operating; independent water-flow indication is normal for this model.
  • Burner runtime contact is OFF; local alarm contact is clear.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
BoilerBurner runtime contact is OFF; local alarm contact is clear.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.