Work order BL-02

Circulator running while startup waits for flow

Boiler · Hydronic systems · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

A boiler will not start although the pump appears healthy. Establish whether water is actually circulating.

Equipment and operating sequence

Illustrative boiler circuit: startup requires measured flow above its documented 20 gpm permissive. The normal operating flow is 30 gpm.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Pump command and motor-running feedback are ON for 90 seconds.
  • Independent flow meter reads 7 gpm; flow permissive remains OFF.
  • Boiler controller reports Waiting for Flow; burner is OFF.
  • Isolation-valve position indicators show their documented operating positions.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Circulation · case readings

Circulator Command
On
Pump motor running Feedback
On
Independent flow Reading
7 gpm

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
CirculatorCommand · CirculationOn—On———
Pump motor runningFeedback · CirculationOn——On——
Independent flowReading · Circulation7gpm————
BurnerStatus · BoilerOff———Off—

Intake observations

  • Pump command and motor-running feedback are ON for 90 seconds.
  • Independent flow meter reads 7 gpm; flow permissive remains OFF.
  • Boiler controller reports Waiting for Flow; burner is OFF.
  • Isolation-valve position indicators show their documented operating positions.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor