Work order BL-03

One heating zone stays cold

Boiler · Hydronic systems · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Other zones heat normally, but one office remains cold even with a full valve command. Identify the failed link.

Equipment and operating sequence

Illustrative two-way zone valve with actuator-position feedback. Its feedback reports actuator rotation, not actual valve-plug position or water flow.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Zone temperature is 63°F against a 70°F occupied target.
  • Heating header supply is 150°F; neighboring zones heat normally.
  • Zone-valve command is 100% and actuator feedback is 100%.
  • Branch flow is 0 gpm; temperatures downstream of the valve remain near 70°F.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Distribution · case readings

Zone temperature Reading
63 °F
Zone target Setpoint
70 °F
Zone valve Command
100 %
Actuator position Feedback
100 %
Branch flow Reading
0 gpm

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Zone temperatureReading · Distribution63°F————
Zone targetSetpoint · Distribution70°F————
Zone valveCommand · Distribution100%100———
Actuator positionFeedback · Distribution100%—100——
Branch flowReading · Distribution0gpm————

Intake observations

  • Zone temperature is 63°F against a 70°F occupied target.
  • Heating header supply is 150°F; neighboring zones heat normally.
  • Zone-valve command is 100% and actuator feedback is 100%.
  • Branch flow is 0 gpm; temperatures downstream of the valve remain near 70°F.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor