Heating water is too cool on a cold morning
Boiler · Sensors and instrumentation · Intermediate
Customer complaint
The boiler follows its target, yet several rooms cannot recover. Check how that target is selected.
Equipment and operating sequence
Illustrative condensing plant reset curve: 110°F supply at 60°F outdoor air, increasing linearly to 150°F at 20°F outdoors; targets are clamped at those endpoints.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- BMS outdoor-air reading is 60°F; its quality flag is Good.
- Calculated water target and measured system supply both read 110°F.
- Multiple zones are below occupied setpoint with heating valves near full open.
- No boiler lockout, capacity limit, or manual target override is active.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Boiler · case readings
- BMS outdoor air Reading
- 60 °F · Good flag
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| BMS outdoor air | Reading · Boiler | 60 | °F | — | — | Good flag | — |
| Water target | Setpoint · Supply header | 110 | °F | — | — | — | No manual target override |
| Measured system supply | Reading · Supply header | 110 | °F | — | — | — | — |
Intake observations
- BMS outdoor-air reading is 60°F; its quality flag is Good.
- Calculated water target and measured system supply both read 110°F.
- Multiple zones are below occupied setpoint with heating valves near full open.
- No boiler lockout, capacity limit, or manual target override is active.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Boiler | No boiler lockout, capacity limit, or manual target override is active. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.