Work order CH-01

Cooling requested, startup remains on hold

Chiller · Electrical · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

An occupied building needs cooling, but the chiller never leaves its flow-verification step. Find the missing response without bypassing the start sequence.

Equipment and operating sequence

Illustrative dedicated-pump plant. Compressor enable requires verified evaporator flow after a 30-second pump-proving interval; the interval has expired.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 14:00: CHW pump command ON; independent run feedback OFF.
  • Evaporator flow 0 gpm; flow permissive FALSE.
  • Cooling request TRUE; chiller available TRUE; leaving water 59°F.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

CHW distribution · case readings

CHW pump start Command
On
Pump run Feedback
Off

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
CHW pump startCommand · CHW distributionOn—On———
Pump runFeedback · CHW distributionOff——Off——
Evaporator flowReading · Evaporator0gpm————
Leaving chilled waterReading · Evaporator59°F————

Intake observations

  • 14:00: CHW pump command ON; independent run feedback OFF.
  • Evaporator flow 0 gpm; flow permissive FALSE.
  • Cooling request TRUE; chiller available TRUE; leaving water 59°F.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.