Work order CH-04

Remote supply temperature stays above target

Chiller · Sensors and instrumentation · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The supervisor reports poor CHW supply temperature despite light compressor loading and satisfied zones. Decide whether cooling performance or measurement is wrong.

Equipment and operating sequence

The chiller controls from its own leaving-water sensor. A separate supervisory sensor is installed beside it in the same well-mixed leaving-water header.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 13:15: supervisor CHWS 50°F; local leaving water 44°F; local target 44°F.
  • Both readings are fresh; compressor load 38%; no active capacity limit.
  • Zone temperatures are stable near their occupied targets.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator · case readings

Supervisor CHWS Reading
50 °F
Local leaving water Reading
44 °F
Local target Setpoint
44 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Supervisor CHWSReading · Evaporator50°F————
Local leaving waterReading · Evaporator44°F————
Local targetSetpoint · Evaporator44°F————
Compressor loadReading · Compressor38%————

Intake observations

  • 13:15: supervisor CHWS 50°F; local leaving water 44°F; local target 44°F.
  • Both readings are fresh; compressor load 38%; no active capacity limit.
  • Zone temperatures are stable near their occupied targets.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.