Condenser water warms despite maximum tower command
Chiller · VFDs and motors · Intermediate
Customer complaint
Condenser entering-water temperature is rising at unchanged load. Determine why additional tower command produces little response.
Equipment and operating sequence
Illustrative belt-driven open cooling tower. Tower approach means leaving tower water minus entering-air wet-bulb temperature; compare at similar flow and heat load.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 15:00: tower leaving water/chiller entering CW 94°F; tower entering water 104°F.
- Entering-air wet bulb 76°F, independently verified; CW flow unchanged.
- Tower fan command 100%; drive output 60 Hz; earlier comparable approach was 7°F.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Condenser system · case readings
- Tower leaving water Reading
- 94 °F
- Tower entering water Reading
- 104 °F
- Tower fan Command
- 100 %
- Tower drive output Feedback
- 60 Hz
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Tower leaving water | Reading · Condenser system | 94 | °F | — | — | — | — |
| Tower entering water | Reading · Condenser system | 104 | °F | — | — | — | — |
| Tower fan | Command · Condenser system | 100 | % | 100 | — | — | — |
| Tower drive output | Feedback · Condenser system | 60 | Hz | — | 60 | — | — |
Intake observations
- 15:00: tower leaving water/chiller entering CW 94°F; tower entering water 104°F.
- Entering-air wet bulb 76°F, independently verified; CW flow unchanged.
- Tower fan command 100%; drive output 60 Hz; earlier comparable approach was 7°F.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Chiller | Tower fan command 100%; drive output 60 Hz; earlier comparable approach was 7°F. | Intake record |