Condensing temperature rises at comparable operating conditions
Chiller · Hydronic systems · Advanced
Customer complaint
Compressor power is increasing although the tower delivers its usual water temperature. Separate tower performance from heat transfer inside the chiller.
Equipment and operating sequence
Illustrative flooded water-cooled chiller. Here condenser approach is saturated condensing temperature minus leaving condenser-water temperature; compare with this machine's clean baseline at matched load and flow.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 14:40: entering CW 86°F; leaving CW 96°F; saturated condensing temperature 108°F; compressor power 140 kW.
- Clean baseline at the same 200-ton cooling load and 577 gpm CW flow: 86°F entering, 95.5°F leaving, 98.5°F saturation, 100 kW.
- Independent temperatures and pressure conversion agree; entering-air wet bulb is unchanged at 78°F.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Condenser system · case readings
- Entering condenser water Reading
- 86 °F
- Leaving condenser water Reading
- 96 °F
- Condensing saturation Reading
- 108 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Entering condenser water | Reading · Condenser system | 86 | °F | — | — | — | — |
| Leaving condenser water | Reading · Condenser system | 96 | °F | — | — | — | — |
| Condensing saturation | Reading · Condenser system | 108 | °F | — | — | — | — |
| Compressor power | Reading · Compressor | 140 | kW | — | — | — | — |
Intake observations
- 14:40: entering CW 86°F; leaving CW 96°F; saturated condensing temperature 108°F; compressor power 140 kW.
- Clean baseline at the same 200-ton cooling load and 577 gpm CW flow: 86°F entering, 95.5°F leaving, 98.5°F saturation, 100 kW.
- Independent temperatures and pressure conversion agree; entering-air wet bulb is unchanged at 78°F.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Chiller | 14:40: entering CW 86°F; leaving CW 96°F; saturated condensing temperature 108°F; compressor power 140 kW. | Intake record |
| Chiller | Clean baseline at the same 200-ton cooling load and 577 gpm CW flow: 86°F entering, 95.5°F leaving, 98.5°F saturation, 100 kW. | Intake record |