Remote pressure looks satisfied while circulation is inadequate
Chiller · Sensors and instrumentation · Advanced
Customer complaint
The distribution pump slows down even as terminal valves open and flow protection stops the chiller. Determine which feedback the pump controller can trust.
Equipment and operating sequence
Illustrative variable-primary plant. Pump control uses remote differential pressure; independent evaporator flow protection remains active. A 4–20 mA transmitter has a physical 0–30 psid range.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 08:50: remote DP display 6.0 psid equals its target; pump command 28%.
- Many terminal valves exceed 95%; evaporator flow falls below this model's minimum.
- Chiller stops on verified low flow; no request to defeat that protection.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
CHW distribution · case readings
- Remote DP Reading
- 6.0 psid
- Remote DP target Setpoint
- 6.0 psid
- Pump request Command
- 28 %
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Remote DP | Reading · CHW distribution | 6.0 | psid | — | — | — | — |
| Remote DP target | Setpoint · CHW distribution | 6.0 | psid | — | — | — | — |
| Pump request | Command · CHW distribution | 28 | % | 28 | — | — | — |
| Chiller run state | Status · Compressor | Stopped on low flow | — | — | — | Stopped on low flow | — |
Intake observations
- 08:50: remote DP display 6.0 psid equals its target; pump command 28%.
- Many terminal valves exceed 95%; evaporator flow falls below this model's minimum.
- Chiller stops on verified low flow; no request to defeat that protection.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Chiller | Chiller stops on verified low flow; no request to defeat that protection. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.