Work order CH-09

Remote pressure looks satisfied while circulation is inadequate

Chiller · Sensors and instrumentation · Advanced

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The distribution pump slows down even as terminal valves open and flow protection stops the chiller. Determine which feedback the pump controller can trust.

Equipment and operating sequence

Illustrative variable-primary plant. Pump control uses remote differential pressure; independent evaporator flow protection remains active. A 4–20 mA transmitter has a physical 0–30 psid range.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 08:50: remote DP display 6.0 psid equals its target; pump command 28%.
  • Many terminal valves exceed 95%; evaporator flow falls below this model's minimum.
  • Chiller stops on verified low flow; no request to defeat that protection.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

CHW distribution · case readings

Remote DP Reading
6.0 psid
Remote DP target Setpoint
6.0 psid
Pump request Command
28 %

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Remote DPReading · CHW distribution6.0psid————
Remote DP targetSetpoint · CHW distribution6.0psid————
Pump requestCommand · CHW distribution28%28———
Chiller run stateStatus · CompressorStopped on low flow———Stopped on low flow—

Intake observations

  • 08:50: remote DP display 6.0 psid equals its target; pump command 28%.
  • Many terminal valves exceed 95%; evaporator flow falls below this model's minimum.
  • Chiller stops on verified low flow; no request to defeat that protection.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
ChillerChiller stops on verified low flow; no request to defeat that protection.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor