Work order RF-01

The display looks satisfied, but the cooler is warm

Refrigeration system · Sensors and instrumentation · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Find why the cooling call ends while independent box readings remain above target.

Equipment and operating sequence

R-134a medium-temperature cooler with TXV; room setpoint 35°F and documented 2°F differential. This is a static teaching snapshot; no product-safety decision is implied.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Controller room temperature: 35°F; independent center-box logger: 42°F at the same timestamp.
  • Cooling demand: OFF; previous cooling cycles ended when the controller reached 35°F.
  • Door closed; last defrost ended 90 minutes ago; both readings marked fresh.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.

Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator / box · case readings

Controller room temperature Reading
35 °F
Independent box logger Reading
42 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Controller room temperatureReading · Evaporator / box35°F————
Independent box loggerReading · Evaporator / box42°F————
Cooling demandCommand · CompressorOff—Off———

Intake observations

  • Controller room temperature: 35°F; independent center-box logger: 42°F at the same timestamp.
  • Cooling demand: OFF; previous cooling cycles ended when the controller reached 35°F.
  • Door closed; last defrost ended 90 minutes ago; both readings marked fresh.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
RefrigerationCooling demand: OFF; previous cooling cycles ended when the controller reached 35°F.Intake record
RefrigerationDoor closed; last defrost ended 90 minutes ago; both readings marked fresh.Intake record