Defrost starts, yet frost remains
Refrigeration system · Sequences of operation · Intermediate
Customer complaint
Identify why repeated defrost events fail to clear the coil.
Equipment and operating sequence
Electric-defrost freezer using a coil termination probe. This example terminates at its documented 50°F probe value, with a separate maximum-time limit. Model-specific limits must replace these authored values if tied to real equipment.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Four defrost starts occurred on schedule; each ended after 90 seconds.
- End reason: temperature termination, not maximum time.
- Termination point rises from 18°F to 50°F; independent coil-tube probe remains below 25°F.
- Heater current during each active event matches the documented normal value.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Defrost duration Reading
- 90 s
- Termination probe range Reading
- 18–50 °F
- Independent coil probe Reading
- <25 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Defrost duration | Reading · Evaporator / box | 90 | s | — | — | — | — |
| Termination probe range | Reading · Evaporator / box | 18–50 | °F | — | — | — | — |
| Independent coil probe | Reading · Evaporator / box | <25 | °F | — | — | — | — |
Intake observations
- Four defrost starts occurred on schedule; each ended after 90 seconds.
- End reason: temperature termination, not maximum time.
- Termination point rises from 18°F to 50°F; independent coil-tube probe remains below 25°F.
- Heater current during each active event matches the documented normal value.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Refrigeration | Four defrost starts occurred on schedule; each ended after 90 seconds. | Intake record |
| Refrigeration | End reason: temperature termination, not maximum time. | Intake record |
| Refrigeration | Termination point rises from 18°F to 50°F; independent coil-tube probe remains below 25°F. | Intake record |