High superheat with intermittent liquid supply
Refrigeration system · Refrigeration · Advanced
Customer complaint
Decide what evidence is needed before calling this a refrigerant shortage.
Equipment and operating sequence
R-134a receiver/TXV cooler at stable load. Evaporator-outlet saturation temperature and tube temperature are paired at the same location; approved charge documentation covers the unchanged installed configuration.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Box: 46°F; evaporator-outlet saturation: 12°F; outlet tube: 42°F, giving 30°F superheat.
- At the TXV inlet, supplied pressure/temperature interpretation shows no reliable subcooling margin.
- Evaporator airflow matches commissioned conditions; cooling demand remains ON.
- Sight-glass bubbles occur, but no charge conclusion is supplied.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Box temperature Reading
- 46 °F
- Evaporator saturation Reading
- 12 °F
- Outlet tube Reading
- 42 °F
- Superheat Reading
- 30 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Box temperature | Reading · Evaporator / box | 46 | °F | — | — | — | — |
| Evaporator saturation | Reading · Evaporator / box | 12 | °F | — | — | — | — |
| Outlet tube | Reading · Evaporator / box | 42 | °F | — | — | — | — |
| Superheat | Reading · Evaporator / box | 30 | °F | — | — | — | — |
Intake observations
- Box: 46°F; evaporator-outlet saturation: 12°F; outlet tube: 42°F, giving 30°F superheat.
- At the TXV inlet, supplied pressure/temperature interpretation shows no reliable subcooling margin.
- Evaporator airflow matches commissioned conditions; cooling demand remains ON.
- Sight-glass bubbles occur, but no charge conclusion is supplied.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.