Temperature spikes follow the delivery window
Refrigeration system · Refrigeration · Intermediate
Customer complaint
Determine whether a repeating high-temperature alarm begins with lost capacity or added load.
Equipment and operating sequence
35°F medium-temperature cooler with TXV and a self-closing personnel door. Use an authored 24-hour evidence timeline; it does not predict product temperature or food safety.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Box rises from 36°F to 46°F between 10:00 and 10:40 each morning.
- Cooling runs continuously during the rise; stable snapshots before and after show normal documented superheat and airflow.
- Door contact reports repeated long-open events during the delivery window.
- No defrost overlaps the rise; outdoor conditions are comparable across the example days.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Box at 10:00 Reading
- 36 °F
- Box at 10:40 Reading
- 46 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Box at 10:00 | Reading · Evaporator / box | 36 | °F | — | — | — | — |
| Box at 10:40 | Reading · Evaporator / box | 46 | °F | — | — | — | — |
| Cooling demand during rise | Status · Compressor | Continuous | — | — | — | Continuous | — |
Intake observations
- Box rises from 36°F to 46°F between 10:00 and 10:40 each morning.
- Cooling runs continuously during the rise; stable snapshots before and after show normal documented superheat and airflow.
- Door contact reports repeated long-open events during the delivery window.
- No defrost overlaps the rise; outdoor conditions are comparable across the example days.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Refrigeration | Box rises from 36°F to 46°F between 10:00 and 10:40 each morning. | Intake record |
| Refrigeration | Cooling runs continuously during the rise; stable snapshots before and after show normal documented superheat and airflow. | Intake record |
| Refrigeration | Door contact reports repeated long-open events during the delivery window. | Intake record |
| Refrigeration | No defrost overlaps the rise; outdoor conditions are comparable across the example days. | Intake record |