Points and signals
Analog signal conversion table
Look up common fractions of a linear 0–10 V, 2–10 V or 4–20 mA span.
Linear input and output checkpoints
| Span | 0–10 VDC | 2–10 VDC | 4–20 mA |
|---|---|---|---|
| 0% | 0 V | 2 V | 4 mA |
| 25% | 2.5 V | 4 V | 8 mA |
| 50% | 5 V | 6 V | 12 mA |
| 75% | 7.5 V | 8 V | 16 mA |
| 100% | 10 V | 10 V | 20 mA |
Field example
A 0–5 in. w.c. transmitter produces 16 mA. It is at 75% span, or 3.75 in. w.c. On a signed −1 to +1 in. w.c. range, the same current represents +0.50 in. w.c.
Procedure
- Check input mode and the transmitter’s physical endpoints.
- Convert measured electrical value to a span fraction. Apply engineering span and offset.
- Test at two separated conditions. Confirm whether square-root extraction or custom scaling changes the mapping.