What you’ll learn
- Identify the high and low reference for a differential measurement.
- Distinguish a pressure reading from a flow measurement.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Identify the pressure reference
A gauge-pressure transmitter compares process pressure with local atmospheric pressure. An absolute transmitter references a vacuum. A differential transmitter compares two ports. A chilled-water supply at 45 psig and return at 38 psig have a difference of 7 psi at those taps. Changing elevation or the location of one reading can change what that subtraction represents. A 0–100 psig sensor and a 0–100 psia sensor can send the same 4–20 mA span while representing different conditions.
Trace both sensing lines
A differential pressure transmitter measures high-port pressure minus low-port pressure. Identify what each port samples. A duct static transmitter referenced to a ceiling plenum answers a different question from a transmitter connected across a filter. A pinched tube can slow a signal. Swapped tubes can reverse it. Compare an independent manometer at the same taps and verify the configured range before interpreting the reading as an equipment fault.
Convert the right quantity
A duct traverse samples velocity across the section. For equal-area samples calculate individual velocities, average them and multiply by clear area. A calibrated differential-pressure flow element often uses flow proportional to the square root of differential pressure at the specified density. A controller taking a square root twice will misreport flow. Ordinary duct static pressure alone does not supply a flow station’s calibration.
Prove water movement independently
For water flow, a balancing valve with pressure taps requires its actual setting and manufacturer curve. A clamp-on ultrasonic meter needs the pipe dimensions, material, fluid and a suitable measurement location. Pump run An observation satisfying a defined criterion. A current switch proves current above its threshold. A duct switch proves pressure differential at its taps. and high differential at a nearly closed valve can coexist with little branch flow. Compare a branch flow measurement and entering/leaving water temperatures under a known load.
- Two pressure taps
- Signed differential
- Configured extraction and coefficient
- Engineering flow
- Independent traverse or flowmeter
Normal operation
Example training conditions
- Across a calibrated airflow pickup at steady air density, a 0.16 in. w.c. differential corresponds to 800 cfm. A separate traverse reads 790 cfm.
- The pickup relationship belongs to that assembly and its installation. Compare both readings with the specified tolerance.
Worked service example
A zone airflow display reads high even when the room has little supply air.
Recorded field evidence · training example
- Equal-area mean duct velocity 500 ft/min.
- Clear rectangular duct 12 × 18 in.
- BAS flow 1,500 cfm under the same conditions.
The clear area is 1.5 ft², giving about 750 cfm. Check duct size, pickup coefficient, sensor zero and whether extraction is performed once. A damper command change would confound the comparison.
Field procedure
- Identify and label the actual taps, units, range and reference.
- Compare pressure at those taps and verify zero using the manufacturer’s permitted method.
- Compare calculated flow with a traverse or independently measured branch flow at the same operating point.
Hands-on exercise
Map the pressure-transmitter signal to engineering units at two points. Identify whether the signal represents linear pressure or already-computed flow before using a square root.
Analog signal converter
Set a 0–100 psi, 4–20 mA transmitter to the signal that represents 75 psi.
Unit 3 service call
The damper shows full travel. The room still has very little air.
Separate the electrical indication, physical movement and measured delivery. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Compare a VAV flow input with a field traverse
Record the independent terminal airflow, displayed flow and active target. Identify the discrepancy before requesting a repair.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Record both pressure references and the unit.
- Use a calibrated relationship or independent flow measurement to establish delivery.
References and further reading
- Fluke · Gauge, absolute and differential pressure ↗
- TSI · Duct traversal for average air velocity and volume ↗
- Spirax Sarco · Principles of flowmetering ↗