What you’ll learn
- Calculate a pressure difference from two taps.
- Calculate duct airflow from average velocity and area.
Before you start · 1 related lesson
0 of 1 prerequisites demonstrated. You can open this lesson at any time.Two locations make a difference
Pressure is force per unit area. The pressure difference between two named measurement points. is pressure at one location minus pressure at another. A fan or pump can raise the fluid pressure. Flow usually spends that pressure rise overcoming resistance through filters, pipes and fittings. Record the order and location of both taps.
Flow needs its own evidence
Flow is volume passing per unit time. For a duct, average air velocity in feet per minute times clear area in square feet gives cubic feet per minute ( Cubic feet per minute, a rate of air delivery. ). One centerline reading can be faster than the average. A properly placed flow meter serves a similar purpose on a water pipe. U.S. gallons per minute is abbreviated gpm.
Changing the load
At comparable air density, raising airflow across the same filter typically increases its pressure drop. A higher drop can also indicate added resistance. Compare with a known baseline at similar flow. A shut valve can support pressure with almost no flow.
- Upstream tap
- Downstream tap
- Duct traverse
Normal operation
Example training conditions
- At a measured 1,000 cfm, the pressure ahead of a clean filter is 0.85 inches of water column and after it 0.65. Drop is 0.20 inches.
- A clear duct area of 2 square feet and mean velocity 500 feet per minute independently give 1,000 cfm.
Worked service example
Filter drop is higher than yesterday.
Recorded field evidence · training example
- Yesterday measured drop 0.20 inches at 1,000 cfm.
- Today measured drop 0.35 inches at 1,350 cfm.
- Taps and instruments are in the same locations.
Flow increased, so a higher drop alone cannot establish a dirty filter. Compare at the previous flow or use the documented filter curve. Check the measured airflow before recommending a change.
Terms in this lesson
- Differential pressure
- The pressure difference between two named measurement points.
- CFM
- Cubic feet per minute, a rate of air delivery.
Hands-on exercise
Inspect the same filter at equal measured flow on two service visits.
Predict before inspection
Virtual bench checkout
Verify your finding in the recorded case to open the bench.
Standalone simulator · free practice
Inspect terminal flow
Locate the terminal airflow point and distinguish its units from duct pressure.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Name the two pressure locations and independently establish flow.
References and further reading
- DOE · Improving Pumping System Performance ↗
- DOE and PNNL · Operations and Maintenance Best Practices, chapter 9 ↗