What you’ll learn
- Compare a surface temperature with dew point.
- Distinguish sensible cooling from removal of moisture.
Before you start · 1 related lesson
0 of 1 prerequisites demonstrated. You can open this lesson at any time.Water in the air
Water vapor is invisible. Water-vapor pressure as a percentage of saturation vapor pressure at the same temperature. (RH) describes how close the air is to saturation at its current temperature. Warm a parcel of air without adding water and its relative humidity usually falls. The saturation temperature for the air’s present water-vapor content. is the temperature at which that parcel reaches saturation when cooled at roughly constant pressure.
Read two air properties together
Psychrometrics relates dry-bulb temperature (an ordinary air thermometer), moisture and energy at a given pressure. Find the measured dry-bulb and RH together on a psychrometric chart. Follow a line of constant moisture content to saturation to read the dew point. A surface below dew point can collect liquid water. A wet cooling coil can therefore cool and dry the air; the removed water has to drain away.
- Room air
- Bare fitting
- Insulated jacket
Normal operation
Example training conditions
- At normal atmospheric pressure, indoor air at 75°F and 50% RH has a dew point near 55°F.
- An exposed 48°F pipe can collect condensate. A 62°F surface in the same air stays above the dew point.
Worked service example
Condensation appears on an insulated water pipe only near one joint.
Recorded field evidence · training example
- Room dew point 59°F, checked locally.
- Exterior insulation surface is 68°F except at the joint, where it is 52°F.
- Moisture forms on that joint while cooling runs.
The joint surface lies below the local dew point, so condensation is plausible. Inspect insulation continuity and the vapor seal. Check for leaks separately before attributing every drop to the air.
Terms in this lesson
- Dew point
- The saturation temperature for the air’s present water-vapor content.
- Relative humidity
- Water-vapor pressure as a percentage of saturation vapor pressure at the same temperature.
Hands-on exercise
Find which surface can collect water from the same room air.
Predict before inspection
Virtual bench checkout
Verify your finding in the recorded case to open the bench.
Standalone simulator · free practice
Inspect the cooling section
Identify where a surface temperature and a local humidity measurement would be needed to test for condensation.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Compare the measured surface temperature with dew point in the air touching it.