Measurements
Electrical measurement reference
Choose a measurement mode and name both terminals before interpreting an electrical reading.
Virtual control-board tests
| Condition and mode | What the reading can establish |
|---|---|
| Source · AC V across X1–X2 | About 24 VAC indicates secondary potential at this test pair. Continue to the loaded circuit to locate a lost feed. |
| Coil · AC V across A1–A2 during a call | Near rated voltage with a released relay suggests checking winding continuity and mechanism under verified isolation. |
| Series contact · AC V across its terminals | A closed conducting contact normally has little drop. When a complete return path exists an open contact can show most of the source voltage. |
| Lock applied · AC V at designated test jacks | The modeled board requires verified 0 VAC at X1–X2. A single pair on this trainer represents only its isolated secondary. |
| Isolated winding · Ω, test link lifted | Compare measured resistance with the correct part and expected temperature. OL can indicate an open path or an exceeded meter range. |
| 2–10 V feedback · DC V from feedback to signal common | 6 V represents halfway through this specified span. Check physical shaft and blade travel separately. |
Field example
An open coil can have 24 VAC across it while passing no winding current. A near-nominal voltage and an isolated OL reading answer different questions about the same component.
Procedure
- On the trainer identify the active circuit, source and reference.
- Use the appropriate voltage mode for energized observations.
- Open and lock the virtual source, verify isolation, then lift the test link for isolated ohms.
- Reconnect and verify the downstream result. Real equipment requires the site’s qualified-person procedures and control of every energy source.