What you’ll learn
- Trace the transformer secondary, series devices, coil and return on a schematic.
- Distinguish an energized coil terminal from a proven run contact.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Read the circuit in its documented rest state
Start at the transformer secondary and follow the wire numbers. Mark the fuse, A condition the sequence requires before an action, such as a ready input before a fan start. contacts, controller output, coil and return. A device designation may appear on several sheets because its coil, auxiliary contacts and main contacts perform different jobs. A normally open contact is drawn open in its unactuated condition. A dry contact provides a switching path and needs a circuit supply. A powered output sources a specified signal. Connecting either one to a digital input requires matching the input’s wiring diagram.
Separate the power circuits
A transformer establishes a secondary voltage between its two secondary terminals. On this board X2 is bonded common. Other equipment can use an ungrounded secondary. The Direct digital control. A local controller reads inputs, runs its program and updates outputs. output closes a path for the 24 VAC K1 coil. K1’s run contact enables the drive through a separate circuit. A contactor has load-rated contacts for its specified motor or other load. Its auxiliary A returned observation such as position or speed. Locate the pickup to see which part of the mechanism it represents. contact can establish position while a failed power pole or drive still prevents rotation.
- X1 · transformer hot
- F1 · fused bus
- S1 · permissive
- DDC · start contact
- A1 · K1 winding
- A2/X2 · return
Normal operation
Example training conditions
- During a normal fan call the simulated 24 VAC source and the voltage across the energized K1 winding both read about 24 VAC. The relay pulls in, its run contact closes and the fan moves air.
- Across a healthy closed series contact the drop is small. Both ends referenced to common can still show nearly the full supply.
Worked service example
A scheduled fan start appears at the workstation while the fan stays idle.
Recorded field evidence · training example
- X1 to X2 24 VAC. DDC output requested On.
- Across K1 A1 to A2 24 VAC. Relay remains released.
- K1 run contact remains open. Drive input indicates Stop.
Voltage reached the winding terminals. Check coil continuity under verified isolation and inspect the relay mechanism. Measuring only X1 or observing the start icon leaves the coil and switched run path untested.
Field procedure
- On the virtual board locate X1 and X2 and identify the common used by the meter.
- Compare source voltage and coil voltage during a call. Record the relay and drive responses.
- Match the next test to the boundary where electrical evidence and physical response disagree. Real panels require qualified, authorized work under site isolation procedures.
Hands-on exercise
Follow the run circuit in the schematic and compare the source and coil readings during a simulated fan call.
Trace the fan relay circuit
Record the live control source and relay coil voltages. Open and lock the simulated disconnect, prove the secondary dead, lift the test link and record the isolated coil resistance. Compare the three readings to locate the failed component.
Scroll the diagram sideways to reach all six terminals, or use the lead selectors.
F1 supplies the controller and the series start path. K1’s normally open contact grants the drive run permission. The enclosed primary and motor feeder are outside the test board.
Digital multimeter
Control disconnect closed · Unlocked · Secondary unverified · Coil link connected.
0 of 3 diagnostic measurements recorded.
Unit 2 service call
The pressure on the graphic disagrees with the field transmitter.
Locate the first disagreement between the field signal, controller conversion and displayed value. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Trace a fan relay on the wiring board
Compare a healthy run circuit with an open safety contact. Record AC voltage on either side of the safety relative to X2 and observe K1.
Open simulator →Knowledge check
Pass at 80%. Every safety item must also pass.
Field takeaways
- Reference each voltage to a named second terminal.
- Follow control voltage, coil action and the separately switched load circuit.