Level 4 · Advanced field device diagnostics

Trace a 24 VAC start circuit

23 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Trace the transformer secondary, series devices, coil and return on a schematic.
  • Distinguish an energized coil terminal from a proven run contact.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Read the circuit in its documented rest state

Start at the transformer secondary and follow the wire numbers. Mark the fuse, contacts, controller output, coil and return. A device designation may appear on several sheets because its coil, auxiliary contacts and main contacts perform different jobs. A normally open contact is drawn open in its unactuated condition. A dry contact provides a switching path and needs a circuit supply. A powered output sources a specified signal. Connecting either one to a digital input requires matching the input’s wiring diagram.

Separate the power circuits

A transformer establishes a secondary voltage between its two secondary terminals. On this board X2 is bonded common. Other equipment can use an ungrounded secondary. The output closes a path for the 24 VAC K1 coil. K1’s run contact enables the drive through a separate circuit. A contactor has load-rated contacts for its specified motor or other load. Its auxiliary contact can establish position while a failed power pole or drive still prevents rotation.

Training-board secondary circuit
  1. X1 · transformer hot
  2. F1 · fused bus
  3. S1 · permissive
  4. DDC · start contact
  5. A1 · K1 winding
  6. A2/X2 · return

Normal operation

Example training conditions

  • During a normal fan call the simulated 24 VAC source and the voltage across the energized K1 winding both read about 24 VAC. The relay pulls in, its run contact closes and the fan moves air.
  • Across a healthy closed series contact the drop is small. Both ends referenced to common can still show nearly the full supply.

Worked service example

A scheduled fan start appears at the workstation while the fan stays idle.

Recorded field evidence · training example

  • X1 to X2 24 VAC. DDC output requested On.
  • Across K1 A1 to A2 24 VAC. Relay remains released.
  • K1 run contact remains open. Drive input indicates Stop.

Voltage reached the winding terminals. Check coil continuity under verified isolation and inspect the relay mechanism. Measuring only X1 or observing the start icon leaves the coil and switched run path untested.

Field procedure

  1. On the virtual board locate X1 and X2 and identify the common used by the meter.
  2. Compare source voltage and coil voltage during a call. Record the relay and drive responses.
  3. Match the next test to the boundary where electrical evidence and physical response disagree. Real panels require qualified, authorized work under site isolation procedures.

Hands-on exercise

Follow the run circuit in the schematic and compare the source and coil readings during a simulated fan call.

Trace the fan relay circuit

Record the live control source and relay coil voltages. Open and lock the simulated disconnect, prove the secondary dead, lift the test link and record the isolated coil resistance. Compare the three readings to locate the failed component.

Supply fan control circuit

120 / 24 VAC transformer · secondary test jacks
F1 fuseS1 safetyDDC DOTest linkRelay coilK1DDCT1Secondary common · bondedDrive input supplyK1 run contactDI-RUNX1 +FSKA1X2 COM

Scroll the diagram sideways to reach all six terminals, or use the lead selectors.

F1 supplies the controller and the series start path. K1’s normally open contact grants the drive run permission. The enclosed primary and motor feeder are outside the test board.

Digital multimeter

23.99 V AC

Isolation and test conditions

Control disconnect closed · Unlocked · Secondary unverified · Coil link connected.

0 of 3 diagnostic measurements recorded.

Unit 2 service call

The pressure on the graphic disagrees with the field transmitter.

Locate the first disagreement between the field signal, controller conversion and displayed value. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%. Every safety item must also pass.

1. On the training board the upstream side of a closed contact is 23.9 VAC to common and its downstream side is 23.9 VAC to the same common. What voltage belongs across this ideal closed contact?
2. Continuity mode is selected while the virtual secondary is energized. What should happen before measuring the winding? · Required for safety
3. During a virtual fan call both ends of K1 are at 24 VAC relative to X2. How much voltage is driving this winding if both values are in phase?
4. A healthy relay picks up and its contacts change state. The separate drive input source is absent. Which part of the start chain still lacks energy?
5. A dry DDC relay changes state correctly on a bench. Which evidence is still needed to explain why the drive run input stays off?

Field takeaways

  • Reference each voltage to a named second terminal.
  • Follow control voltage, coil action and the separately switched load circuit.

References and further reading