Electrical measurement reference

Choose a measurement mode and name both terminals before interpreting an electrical reading.

Virtual control-board tests

Virtual control-board tests
Condition and modeWhat the reading can establish
Source · AC V across X1–X2About 24 VAC indicates secondary potential at this test pair. Continue to the loaded circuit to locate a lost feed.
Coil · AC V across A1–A2 during a callNear rated voltage with a released relay suggests checking winding continuity and mechanism under verified isolation.
Series contact · AC V across its terminalsA closed conducting contact normally has little drop. When a complete return path exists an open contact can show most of the source voltage.
Lock applied · AC V at designated test jacksThe modeled board requires verified 0 VAC at X1–X2. A single pair on this trainer represents only its isolated secondary.
Isolated winding · Ω, test link liftedCompare measured resistance with the correct part and expected temperature. OL can indicate an open path or an exceeded meter range.
2–10 V feedback · DC V from feedback to signal common6 V represents halfway through this specified span. Check physical shaft and blade travel separately.

Field example

An open coil can have 24 VAC across it while passing no winding current. A near-nominal voltage and an isolated OL reading answer different questions about the same component.

Procedure

  1. On the trainer identify the active circuit, source and reference.
  2. Use the appropriate voltage mode for energized observations.
  3. Open and lock the virtual source, verify isolation, then lift the test link for isolated ohms.
  4. Reconnect and verify the downstream result. Real equipment requires the site’s qualified-person procedures and control of every energy source.