Level 5 · Control logic and sequence development

Read comparators, timers and hysteresis across scans

22 minutes · Intermediate

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Predict the retained state between cut-in and cut-out thresholds.
  • Determine whether an on-delay has actually earned enough uninterrupted time.
Before you start · 1 related lesson0 of 1 prerequisites demonstrated. You can open this lesson at any time.

A temperature between thresholds needs a history

The example cooling stage turns on at or above 76°F and turns off at or below 73°F. Between 73°F and 76°F it keeps its previous state. The 3°F separation is . A separate heating/cooling is a region where neither mode calls. Similar names can represent different implementations, so read both thresholds, the comparison operators and the behavior when neither comparison is true.

A timer has an input, elapsed time and an output

A non-retentive on-delay asserts its output after its input has stayed true for the preset time. A false input resets its elapsed time. An off-delay can keep the output active after the input falls. A minimum-off lockout blocks restart for a specified duration after a stop. Record the scan interval and timer enable alongside the raw process value. A graph sampled once per minute can hide the brief dropout that reset a 30-second timer.

Qualify a sustained high temperature
  1. Read temperature
  2. Compare to high limit
  3. Enable on-delay
  4. Require uninterrupted interval
  5. Report qualified condition

Normal operation

Example training conditions

  • An on-delay begins at 10:00:00 and requires ten continuous seconds. With permission still present at 10:00:10, the timed output becomes true at the first scan meeting that interval.
  • For a non-retentive timer a false input before the deadline clears elapsed time. Switching hysteresis instead uses different thresholds for rising and falling values.

Worked service example

A high-temperature alarm never reports even though the trend crosses its threshold twice.

Recorded field evidence · training example

  • Training alarm threshold 80°F, non-retentive on-delay 30 s.
  • Above threshold for 19 s, below for 2 s, above for 23 s.
  • Alarm output remains false.

Neither uninterrupted event lasts 30 s. The second needs 7 more seconds. Shorten the trend sample interval to see each transition before changing the alarm delay.

Field procedure

  1. Record thresholds, direction, previous stage state and timer type.
  2. Trend the timer enable at a resolution adequate to capture resets.
  3. Reproduce a short excursion, a qualifying excursion and a normal return in the simulator.

Hands-on exercise

Follow a timing block’s input and output across scans. Interrupt the input before the delay expires and observe the elapsed or output state.

Function-block commissioning

Connect the request and permission so both must remain on for three seconds before EF-01 receives a start. Losing either input must immediately remove the start. Each scan advances the same simulated controller and exhaust plant by one second.

  1. InputsRequest · AHU occupancyPermit · exhaust enable
  2. On delay
  3. Binary outputEF-01.EF-CMD
Scans 0 · gate — · timer — · output —

Unit 4 service call

The operator enabled the AHU. Should the fan have started yet?

Predict which transition is permitted and when its proof timer starts. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. A ten-second off-delay holds an output after occupancy drops. Occupancy drops at second 18 and stays false. At what second should the output turn off on a one-second scan aligned to these times?
2. A nuisance alarm should trigger only after continuous loss of proof. Which test distinguishes a non-retentive delay from one that wrongly accumulates short losses?
3. A non-retentive 20 s on-delay sees true for 12 s, false for one complete scan and true for another 9 s. How many more uninterrupted seconds are needed?
4. A stage turns on below 38°F and off above 42°F. The input is 40°F. What other information determines its present state?
5. Cooling turned on at 76°F and turns off at 73°F. The input falls from 77°F to 74°F. What does the stage do?

Field takeaways

  • Record the preceding state when interpreting hysteresis.
  • Test brief and sustained changes to distinguish timer behavior.

References and further reading

Technician handbook