Original module 02 assessment

Electrical and Controls Fundamentals

Read a control circuit, choose a reference terminal and translate the measured signal into a defensible service finding.

Module examination

Pass at 80%.

1. On the training board the upstream side of a closed contact is 23.9 VAC to common and its downstream side is 23.9 VAC to the same common. What voltage belongs across this ideal closed contact?
2. A linear 4–20 mA transmitter covers −1 to +3 in. w.c. What pressure does 8 mA represent?
3. The drawing specifies a 10 kΩ thermistor. Two possible curves both read 10 kΩ at 25°C. What distinguishes the choices?
4. An unpowered relay measures 12 Ω in circuit and OL with one coil lead lifted. What explains the first result?
5. A start command is ON, the coil terminals measure 24 VAC under demand, and the armature is released. Which check distinguishes a broken winding from a downstream contact problem?
6. A receiving actuator maps 2–10 VDC to 0–100% travel. What travel does a 4.0 V signal request?
7. At 15 mA on a linear 4–20 mA transmitter spanning 0–160 psi, what pressure corresponds to the signal?
8. A dry DDC relay changes state correctly on a bench. Which evidence is still needed to explain why the drive run input stays off?