Original module 04 assessment

Control Logic and Programming

Read a program one decision at a time, predict its output and test the physical result across several controller scans.

Module examination

Pass at 80%.

1. A continuous-proof timer is set for 12 seconds. Proof arrives at second 4, drops at second 12, and returns at second 15. When can the enable first become true?
2. Cooling turned on at 76°F and turns off at 73°F. The input falls from 77°F to 74°F. What does the stage do?
3. For the example reset of 160°F at 20°F outdoors and 120°F at 60°F outdoors, calculate the target at 35°F outdoors.
4. An air-temperature loop spends ten minutes at its output limit. When capacity returns, the valve stays open past setpoint. Which observation tests integral windup?
5. For (Occupied OR Extension) AND Ready AND NOT Trip, inputs are false, true, true and false respectively. What result follows?
6. A correct 15 s proof timer is visible. FanAlarm still activates instantly. Which connection should you trace first?
7. A fan’s own start condition requires the airflow switch to be proven while the fan is initially at rest. Which sequence change resolves the circular dependency in the training program?
8. A controller holds its output at 100% while a verified process reading stays below a heating target. Which next check is most informative?
9. A non-retentive 20 s on-delay sees true for 12 s, false for one complete scan and true for another 9 s. How many more uninterrupted seconds are needed?
10. RunRequest stays true. FanProof remains false for 14 s, true for one scan, then false for 6 s. For the example 15 s non-retentive delay, how much longer must proof remain missing?