Module examinationPass at 80%. 1. A continuous-proof timer is set for 12 seconds. Proof arrives at second 4, drops at second 12, and returns at second 15. When can the enable first become true?Answer (s)2. Cooling turned on at 76°F and turns off at 73°F. The input falls from 77°F to 74°F. What does the stage do?Turns off because 74 is below its on threshold.Remains on because it has not reached cut-out.Changes state each controller scan.3. For the example reset of 160°F at 20°F outdoors and 120°F at 60°F outdoors, calculate the target at 35°F outdoors.Answer (°F)4. An air-temperature loop spends ten minutes at its output limit. When capacity returns, the valve stays open past setpoint. Which observation tests integral windup?A trend of error, integral contribution and limited output togetherThe proportional gain value by itselfA single room temperature after the complaint5. For (Occupied OR Extension) AND Ready AND NOT Trip, inputs are false, true, true and false respectively. What result follows?Stopped because occupancy is mandatory.Start requested because the extension qualifies and both gates pass.Stopped because a false trip inhibits the run.6. A correct 15 s proof timer is visible. FanAlarm still activates instantly. Which connection should you trace first?The workstation restoral timestamp.The alarm writer’s source, comparing the raw missing-proof Boolean with the timer’s Q output.The fan’s pressure setpoint reset curve.7. A fan’s own start condition requires the airflow switch to be proven while the fan is initially at rest. Which sequence change resolves the circular dependency in the training program?Permanently force the airflow input.Start when permissives pass, then evaluate airflow within the approved proof interval.Remove the fan safeties.8. A controller holds its output at 100% while a verified process reading stays below a heating target. Which next check is most informative?Add derivative filtering before examining the plant.Verify delivered heat, valve travel, flow and equipment limits.Double the integral gain.9. A non-retentive 20 s on-delay sees true for 12 s, false for one complete scan and true for another 9 s. How many more uninterrupted seconds are needed?Answer (s)10. RunRequest stays true. FanProof remains false for 14 s, true for one scan, then false for 6 s. For the example 15 s non-retentive delay, how much longer must proof remain missing?Answer (s)Submit assessmentApply this material in Unit 4Follow the sequence of operationApply this material in Unit 8Diagnose with trends before changing a control loopReturn to Learning Center