Original module 07 assessment

Advanced HVAC Control Strategies

Choose reset and staging responses from real load evidence while preserving humidity, ventilation and equipment limits.

Module examination

Pass at 80%.

1. A training reset target is 1.36 in. w.c., with an upper limit of 1.40. A qualified request adds 0.10. What target reaches the inner fan loop?
2. With outdoor air at 45°F and return air at 75°F, what is the ideal mixed temperature at 40% outdoor air?
3. An optimal-stop trial saves half an hour of cooling but a late-occupied zone exceeds its limit. What should the comparison include?
4. Several coils meet their targets. One is fully open with very low measured branch flow while plant supply temperature is correct. Which evidence comes next?
5. A terminal meets design airflow but the space remains warm. Which evidence most directly distinguishes an overly warm primary supply from inadequate flow?
6. An illustrative linear hot-water reset delivers 170°F at 10°F outdoors and 130°F at 50°F outdoors. What is the target at 25°F outdoors?
7. Most VAV dampers throttle near minimum. One terminal requests more pressure, has a wide-open actuator and nearly zero measured flow. What should precede a permanent pressure increase?
8. Under ideal fan affinity assumptions, what percentage of original shaft power is required at 80% speed?
9. At a steady 120 tons, measured total plant input is 96 kW. What is the observed plant efficiency?